GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
TIMER SETPOINTS
Timer delays are displayed in the windows detailed below with selections
'type'= 'TIMERS and 'view'= 'LATEST VALUE'.
All timer delays count down to zero in tenths of a minute :-
Timers are adjusted using 'raise', 'lower', 'next', 'accept' when 'view'= setpoints
Adjustable timers are available for:-
Timer
Window
Range and description
Stage-Up (u)
SUCTION
0.5 to 12min
Time Compressor at 100% before
allowing next compressor to start.
Stage-Down (d)
DISCHARGE
0.5 to 10min
Time compressor at minimum load or
time at 50% if in slide balance mode
before stopping.
Set at 10.0 min = none,
NO STOP AT MINIMUM,
MANUAL STOP ONLY
N.B. To exit
none
setting =
Discharge, Timer, Setpoint, Lower, Accept.
Pre-Lubrication
(p)
OIL
0.0 to 5.0min
Oil pump run before compressor starts.
At-minimum signal must be present at
the end of this timer or a 'S-UP' trip is
displayed before the motor is started.
On a siphon system this timer is
restarted with the motor and inhibits
LOW oil differential pressure alarms and
trips whilst it is still active.
Pump-off-after
Stop (o)
FILTER
0.0 to 5.0min
Oil pump run delay after compressor
stops until at-minimum received.
Capacity load
delay
CAPACITY%
0.5 to 5.0min
This timer determines the interval
between loading/unload pulses when the
control is close to ( <0.3 bar) the control
setpoint. This delay is also used after
starting motor before loading pulses
are started.
After-Stop
LOAD %
1.0 to 5.0min
the minimum time required after stop
before allowing another restart.
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...