Page 67
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
Setup / Commissioning Parameters
PRESSURES
Display
Window
‘type’
selection
‘view’
selection
Settings
unit
Actual
Setting
Default
Setting
Min
Max
SUCTION
PRESSURE
SETPOINT
Suction Pressure setpoint
(Fixed Control Diff +/ - 0.1bar)
NB When in ‘rP5c’ Display is a
duplicate of
Filter/Equivalent/Setpoint.
bar
-0.6b
24.0b
DISCHARGE
PRESSURE
SETPOINT
ONLY If ‘FANS’
selected, condenser
fan1 on @ setpoint,
off @ 0.5b below setpoint
bar
5.0
20.0
CAPACITY
PRESSURE
SETPOINT
Economiser on at slide greater than
%
0
100
LOAD
PRESSURE
SETPOINT
% load current above which capacity
unload pulses are started
%
50
99
SUCTION
PRESSURE
LOW ALARM
Stops compressor on low suction
pressure (Automatic Restart)
bar
-1.0b
5.0b
CAPACITY
PRESSURE
LOW ALARM
Load Sharing Compressors
Minimum slide % at which a load-
sharing compressor is allowed before it
auto-stops after stage-down time.
Load Sharing OFF When set to 0%
%
0
80
SUCTION
PRESSURE
HIGH ALARM
hi-alarm suction pressure
bar
0.0b
20.0b
DISCHARGE
PRESSURE
HIGH ALARM
hi-alarm disc pressure (unload)
bar
0.0b
23.0b
CAPACITY
PRESSURE
HIGH ALARM
Maximum slide capacity above which
the compressor inhibits loading pulses.
%
50
110
LOAD
PRESSURE
HIGH ALARM
% load current above which alarm
generated
%
75
100
SUCTION
PRESSURE
LOW TRIP
Low-trip suction pressure (Comp Stop
Manual Reset Required.)
bar
-1.0b
5.0b
CAPACITY
PRESSURE
LOW TRIP
Compressor Auto-stops when slide
below
Capacity, Pressure, Low-trip % ,
for stage down time period.
No Action When Set to Zero 0%
Restart after Starts/Hour timer
SH
%
0
100
LOAD
PRESSURE
LOW TRIP
low-trip motor current
%
-11
50
SUCTION
PRESSURE
HIGH TRIP
high-trip suction pressure
bar
0.0b
20.0b
DISCHARGE
PRESSURE
HIGH TRIP
high-trip discharge pressure
bar
0.0b
23.0b
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...