Page 38
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
STARTING
After a start request has been made the Oil pump is started. Provided a pump
running signal has been received, the oil differential limit is satisfied,(within the oil
differential delay time ‘dt’), and the slide is at minimum the motor will then start.
If the slide is not at minimum when the pump is started then the following
procedure is completed:-
1. The un-load solenoid is energised.
2. If the slide returns to minimum within the differential delay time,’dt’, then motor
start will proceed as above.
3. When the slide does not return to minimum within ‘dt’ the pump continues to run
until the slide is at minimum or the pump pre-lube delay is exceeded.
4. If the slide is at minimum then the pump is stopped and a motor re-start delay
time is enforced before a normal starting procedure is attempted. This allows
excess oil in the compressor to drain away.
5. If the slide has not made minimum after the pre-lube delay the compressor will
go to the tripped state
'S-uP'/'trip'.
6. If the pump run signal is not present within ‘dt’ the compressor goes to the
tripped state
'PunP'/'trip'
If the motor running signal,(motor in delta), is not received within thirty seconds the
compressor will go to the tripped state
'nnot'/'trip'.
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...