Page 60
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
TRANSDUCER SETUP & CALIBRATION
TRANSDUCER SETUP
Transducer zero, scale and voltage ranges must be selected prior to calibration
and is done as follows:-
Enter set-up as described in earlier section:
“
@:@
view
”
= “SYSTEM”
“
@:@
type
”
= “SAFETY TRIPS”
SUCTION
OIL
==sE tUP=
DISCHARGE
FILTER
==== =yEs
“
@
accept
” “
@:@
next
”
DISCHARGE
FILTER
==== AnAL
“
@
accept
”
DISCHARGE
FILTER
==== P=nn
nn = P000 = 0-100mV transducer (P -zero)
nn = P004 = 4-20mA transducer
“
@
next
”
DISCHARGE
FILTER
==== C=nn
nn = is slide voltage range 0-10V dc (C -scale)
C 05 = 0-5V dc
C 41 is a slide giving only 4.1 volts due to line
losses instead of 5.0 volts
C100 is 4-20mA slide input selection
(Also for 4-20mA Fit Link LKV2 adjacent TB7)
“
@
next
”
DISCHARGE
FILTER
==== tnnn
nnn = is the current transformer rating (T - size)
eg for a CT of 300:5 then nnn = 300
“
@
next
”
DISCHARGE
FILTER
==== rnnn
nnn = is the maximum rated motor (R - size)
load in Amps
eg For a 250Amp compressor nnn = 250
“
@
next
”
To change any ‘Anal’ (Analog) setting use the following procedure;
“
@
raise
”
or
“
@
lower
”
until correct value is displayed
SUCTION
OIL
“
@
accept
”. “
@
next
”
==sE tUP=
DISCHARGE
FILTER
==== donE
“
@
accept
” “
@
RESET
”
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...