Page 65
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
Main Set-up/ Commissioning Parameters Cont’d
Syst
units
Actual
setting
Default
setting
Min
Max
Motor starts per hour
SH
SH02
SH19
Loading Valve Polarity
LPoS = Loading Valve is normally OPEN
Lneg = Loading Valve is normally CLOSED
L
LPoS
LPoS
Lneg
Unloading Valve Polarity
UPoS = Loading Valve is normally OPEN
Uneg = Loading Valve is normally CLOSED
U
UPoS
UPoS
Uneg
Load pulse
width, as a % of 6 seconds
Load Pulse Interval Controlled by
Capacity Timer Setpoint
%
LP
LP02
LP99
Starting Pulse
Initial Loading pulse sent on receipt of compressor run signal,
until at minimum signal removed.
Output is % of 6 seconds
No Initial pulse if set to 0%
%
SP
SP00
SP99
LPSt =
pulse stop @ Max,
LPPU =
cont’d pulse @ Max
LP
LPSt
LPPU
Unload pulse
width, as a % of 6 seconds
Load Pulse Interval Controlled by
Capacity Timer Setpoint
%
UP
UP02
UP99
Pump Type Selection
PunP,
Pump Run Compressor
(Oil Differential, Oil P3 to Discharge P2)
P-ST,
Pump Start Compressor
(Oil Differential, Oil P3 to Suction P1)
no-P,
No Pump Compressor
(Oil Differential, Oil P3 to Suction P1)
FiLt, Special, Contact Guardian.
PunP
FiLt
Oil differential trip delay
secs
dt
dt00
dt99
( IF bY- P )
Bypass delay time, On 4secs before comp starts &
On at compressor STOP
. (output=VI-2, RL9)
secs
bt
bt05
bt99
( IF 2Fan ),
Fan 2 additional cut in above setpoint
bar
bF
bF0.5
bF9.9
NOT USED
Lb
Lb1.0
Lb9.9
Economiser retry after back off
mins
Et
Et00
Et99
Motor Inverter Minimum Start Speed
[Analogue Output (A OP2)]
Set To St00 if Not Used
%
St
St00
St99
( If Speed Inverter ),
Speed Increment
%
Si
Si01
Si20
Auxiliary relay operation mode
noUi/Ui-1/Ui-2/both/Vi-A/2-SP/Stby/by-P/2FAn
Refrigeration input positive/negative for ON
r
rPoS
rnEg
Send
OFF
command on compressor trip
(via comms)
CnoA
= no action,
CoFF =
Send Off Signal
C
CnoA
CoFF
Trip inputs positive
tPoS
/ negative
tneg
to trip
t
tPoS
tneg
Gas type (R22, Ammonia NH3 or 404A)
r22
404A
Analogue input 5 selection None/Pres4-20/Ptr1000ohm
none
none
Ptr
Filter Differential Calculation
Fstd,
Filter Standard
, Diff. Calc. = P4- P3
Filter Located after Pump P4 and before Oil Manifold P3
Fdis,
Filter Discharge
, Diff. Calc. = P2- P4
Filter Located after Discharge P2 and before Pump P4
F
Fstd
Fstd
Fdis
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...