Auto VI Commissioning Parameters
Aui
only displayed if ‘VI-A’ is selected
units
Actual
settin
g
Defaul
t
settin
g
Min
Max
Compressor Type
Specifies the Howden compressor type:
1 = XRV163/165
4 = XRV204/145
NB. Only types 1 and 4 are currently supported. (See
attached data sheet for Guardian defaults)
Ct
Ct00
Ct06
Maximum Capacity Travel.
This is normally defaulted for the Compressor type
selected. However, this may vary depending on Howden
configuration, so check with manufacturers data sheets.
(See attached data sheet for Guardian defaults)
mm
C
C000
C255
Maximum Slide Stop
This is normally defaulted for the Compressor type
selected. However, this may vary depending on Howden
configuration, so check with manufacturers data sheets.
(See attached data sheet for Guardian defaults)
mm
U
U000
U255
Initial VI Setting.
Capacity slide percentage at which auto variable VI is
applied.
(See attached data sheet for Guardian defaults)
%
in
in45
in99
Period Auto VI is applied
(Adjustable in 0.1 minute steps, ie 6 seconds)
Dependant on application. Recommend starting at 0.5 (30
seconds)and observe system response. If too erratic
increase time.
Mins
P
P0.0
P25.5
Fixed VI Setting
If a fixed VI condition is required then this may be
adjusted to give the required slide stop.
When set to 0.0 then Auto variable VI is in action.
Fi
Fi0.0
Fi5.0
Note: For Auto VI to work successfully the capacity slide must have been calibrated at
the lowest VI setting.
Guardian Default Data for Howden Compressors.
Compressor
Model
Compressor
Type
Capacity
travel
(mm)
Slide
Stop
(mm)
Initial VI
Setting(%)
VI
minimum
VI
maximum
Parked
position
(mm)
XRV163/165
Ct 01
C150
U47
In 70
2.6
5.0
52
XRV204/145
Ct 04
C152
U54
In 64
2.6
5.0
59
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...