Page 10
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
The compressor may be selected to operate in one of three control modes:-
MANUAL, LOCAL or REMOTE MODES.
Safety interlocks, alarm, trip, startup and shutdown sequence controls are automatic in
all three modes.
In
MANUAL
mode, the each compressor may be individually started and stopped and the
pack capacity raised and lowered by operator pushbutton control from the local panel.
In
LOCAL
automatic mode, the compressor is started and stopped under control of the
suction pressure setpoint.
REMOTE
automatic mode allows up to six RCC-40 units to be connected via a two-wire
communication link (RS485) to provide 6-unit system control.