“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
SECTION 3.4
DIAGNOSTIC TESTS
PART 3
Page 55
PROCEDURE:
1. On the generator panel, set the AUTO-OFF-MANUAL
switch to OFF.
2. Turn OFF the utility power supply to the transfer switch,
using whatever means provided.
3. See Figure 5. Remove fuses F1 and F2 from the fuse
holder.
4. Inspect and test fuses for blown condition.
RESULTS:
1. Replace blown fuse(s).
TEST 11- TEST LIMIT SWITCH XA1
DISCUSSION:
When the transfer switch main contacts are actuated
to their “Utility” position, limit switch XA1 should be
mechanically actuated to its open position. On trans-
fer to the “Standby” position, the limit switch should
actuate to its “Closed” position. If the switch does not
actuate to its “Closed” position, retransfer back to
“Utility” will not occur.
PROCEDURE:
1. With the standby generator shut down, set the AUTO-
OFF-MANUAL switch to OFF.
2. Turn OFF the utility power supply to the transfer switch,
using whatever means provided.
3. To prevent interaction, disconnect Wire No. 126 and Wire
“A” from the limit switch terminals.
4. Set a VOM to its “Rx1 “ scale and zero the meter.
5. Connect the VOM test leads across the two limit switch
terminals from which Wires “A” and 126 were removed.
6. Manually actuate the main contacts to their “Standby”
position. The VOM should indicate CONTINUITY.
7. Manually actuate the main contacts to their “Utility” posi-
tion. The VOM should read INFINITY.
RESULTS:
Replace limit switch XA1 if it checks bad.
NOTE: Problems with transfer switch operation
can also be caused by (a) defective wiring
between the generator and transfer switch, or (b)
a defective component in the generator’s control
board. See Part 4, “DC Control - Units with Liquid
Cooled Engine”.
Содержание 4721
Страница 60: ...PART 3 Page 56 V TYPE PREPACKAGED TRANSFER SWITCHES SECTION 3 4 DIAGNOSTIC TESTS...
Страница 98: ...PART 4 Page 94 DC CONTROL LIQUID COOLED ENGINE UNITS SECTION 4 4 DIAGNOSTIC TESTS...
Страница 108: ...Page 104 PART 9 ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE DRAWING 0F0015 A 1 of 2...
Страница 109: ...ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE PART 9 Page 105 DRAWING 0F0015 A 2 of 2...
Страница 112: ...PART 9 Page 108 ELECTRICAL DATA WIRING DIAGRAM 1 5 LITER LIQUID COOLED ENGINE DRAWING 0E0343 B...
Страница 115: ......