TEST 14 - CHECK AND ADJUST
VOLTAGE REGULATOR
DISCUSSION:
For additional information, refer to description and
components Section 2.1.
PROCEDURE:
With the frequency between 59.5-60.5 Hertz, slowly
turn the slotted potentiometer (Figure 10) until line
voltage reads 238-242 volts.
NOTE: You must remove the access panel on
top of the control panel to adjust the voltage
regulator.
NOTE: The voltage regulator is housed above the
generator control panel. The regulator maintains a
voltage in direct proportion to frequency at a 2-to-
1 ratio. For example, at 62 Hertz, line-to-neutral
voltage will be 124 volts.
Figure 10. Voltage Adjustment Potentiometer
RESULTS:
1. If the frequency and voltage are now good, discontinue
tests.
2. If frequency is now good but voltage is high or low, go to
Problem 1, Test 5.
TEST 15 - CHECK VOLTAGE AND
FREQUENCY UNDER LOAD
DISCUSSION:
It is possible for the generator AC output frequency
and voltage to be good at no-load, but they may drop
excessively when electrical loads are applied. This
condition, in which voltage and frequency drop exces-
sively when loads are applied, can be caused by (a)
overloading the generator, (b) loss of engine power,
or (c) a shorted condition in the stator windings or in
one or more connected loads.
PROCEDURE:
1. Connect an accurate AC frequency meter and an AC
voltmeter across the stator AC power winding leads.
2. Start the engine, let it stabilize and warm-up.
3. Apply electrical loads to the generator equal to the rated
capacity of the unit.
4. Check the AC frequency and voltage. Frequency should
not drop below approximately 59 Hertz. Voltage should
not drop below about 230 volts (plus or minus 2 per-
cent).
RESULTS:
1. If frequency and voltage drop excessively under load, go
to Test 16.
2. If frequency and voltage under load are good, discontin-
ue tests.
TEST 16 - CHECK FOR OVERLOAD
CONDITION
DISCUSSION:
An “overload” condition is one in which the generator
rated wattage/amperage capacity has been exceed-
ed. To test for an overload condition on an installed
unit, the best method is to use an ammeter. See
“Measuring Current” in Section 1.4.
PROCEDURE:
Use a clamp-on ammeter to measure load current
draw, with the generator running and all normal elec-
trical loads turned on.
RESULTS:
1. If the unit is overloaded, reduce loads to the unit’s rated
capacity.
2. If unit is not overloaded, but rpm and frequency drop
excessively when loads are applied, go to Test 17.
TEST 17 - CHECK ENGINE CONDITION
DISCUSSION:
If engine speed and frequency drop excessively
under load, the engine may be under-powered. An
under-powered engine can be the result of a dirty air
cleaner, loss of engine compression, faulty carburetor
settings, incorrect ignition timing, etc.
PROCEDURE:
For engine testing, troubleshooting and repair proce-
dures refer to following manual:
• P/N 0C1947 - Service Manual 1.5 Liter Gas Engine
PART 2
Page 38
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.4
DIAGNOSTIC TESTS
Содержание 4721
Страница 60: ...PART 3 Page 56 V TYPE PREPACKAGED TRANSFER SWITCHES SECTION 3 4 DIAGNOSTIC TESTS...
Страница 98: ...PART 4 Page 94 DC CONTROL LIQUID COOLED ENGINE UNITS SECTION 4 4 DIAGNOSTIC TESTS...
Страница 108: ...Page 104 PART 9 ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE DRAWING 0F0015 A 1 of 2...
Страница 109: ...ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE PART 9 Page 105 DRAWING 0F0015 A 2 of 2...
Страница 112: ...PART 9 Page 108 ELECTRICAL DATA WIRING DIAGRAM 1 5 LITER LIQUID COOLED ENGINE DRAWING 0E0343 B...
Страница 115: ......