PART 2
Page 28
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.3
TROUBLESHOOTING FLOW CHARTS
TEST 12 - CHECK
AC OUTPUT
FREQUENCY
TEST 2 - CHECK
AC OUTPUT
VOLTAGE
TEST 13- ADJUST
VOLTAGE
REGULATOR
LOW
LOW
STOP TESTS
FREQUENCY O.K.,
BUT VOLTAGE LOW
FREQUENCY O.K.,
BUT VOLTAGE IS
STILL LOW
GO TO “PROBLEM 1”
FLOW CHART - START
AT “TEST 5 - F/E”
VOLTAGE AND FREQUENCY O.K.
FREQUENCY AND
VOLTAGE O.K.
Problem 2 - Generator Produces Low Voltage at No-Load
TEST 13 - CHECK AND
ADJUST GOVERNOR
BOARD AND
STEPPER MOTOR
TEST 12 - CHECK
AC OUTPUT
FREQUENCY
TEST 2 - CHECK
AC OUTPUT
VOLTAGE
TEST 14 - ADJUST
VOLTAGE
REGULATOR
HIGH
HIGH
DISCONTINUE TESTING
DISCONTINUE TESTING
FREQUENCY O.K.,
BUT VOLTAGE HIGH
FREQUENCY O.K.,
BUT VOLTAGE HIGH
FREQUENCY O.K.,
BUT VOLTAGE IS
STILL HIGH
VOLTAGE AND
FREQUENCY O.K.
FREQUENCY AND
VOLTAGE O.K.
REPLACE DEFECTIVE
VOLTAGE REGULATOR
Problem 3 - Generator Produces High Voltage at No-Load
TEST 13 - CHECK AND
ADJUST GOVERNOR
BOARD AND
STEPPER MOTOR
Содержание 4721
Страница 60: ...PART 3 Page 56 V TYPE PREPACKAGED TRANSFER SWITCHES SECTION 3 4 DIAGNOSTIC TESTS...
Страница 98: ...PART 4 Page 94 DC CONTROL LIQUID COOLED ENGINE UNITS SECTION 4 4 DIAGNOSTIC TESTS...
Страница 108: ...Page 104 PART 9 ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE DRAWING 0F0015 A 1 of 2...
Страница 109: ...ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE PART 9 Page 105 DRAWING 0F0015 A 2 of 2...
Страница 112: ...PART 9 Page 108 ELECTRICAL DATA WIRING DIAGRAM 1 5 LITER LIQUID COOLED ENGINE DRAWING 0E0343 B...
Страница 115: ......