“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
SECTION 3.1
DESCRIPTION & COMPONENTS
PART 3
Page 43
Figure 6. Transfer Switch Terminal Block
Terminals used on the terminal block are identified as
Utility 1 and 2; Load 1 and 2; 23 and 194.
UTILITY 1 AND 2:
Interconnect with identically labeled terminals in the
generator’s control board. This is the “Utility Voltage”
signal to the control board. The signal is delivered to
a “step-down” transformer in the control module
assembly and the resultant reduced voltage is then
delivered to the circuit board. Utility 1 and 2 power is
used by the control board as follows:
• If utility source voltage should drop below a preset
level, control board action will initiate automatic
cranking and startup, followed by automatic
Transfer to the “Standby” source.
• Utility source voltage is used by the control board to
operate a battery “trickle charge” circuit which helps
to maintain battery state of charge during non-oper-
ating periods.
LOAD 1 AND 2:
The control board is equipped with a “7-Day
Exerciser” circuit which will start the generator and let
it “exercise” once every seven (7) days on a prese-
lected day and at a preselected time of day. The
“Load 1 and 2” terminals provide power to operate the
exerciser timer clock.
TERMINALS 23 AND 194:
These terminals connect the transfer relay to the gen-
erator’s control board. See Section 3.1, “Transfer
Relay”.
FUSE HOLDER
The fuse holder holds four (4) fuses, designated as
fuses F1, F2, F3 and F4. Each fuse is rated 2
amperes.
FUSES F1 AND F2:
These two fuses protect the terminal boards “Utility 1
and 2” circuit against overload.
FUSES F3 AND F4:
These two fuses protect the “Load 1 and 2” circuit
against overload.
Figure 7. The Fuse Holder
N1A
N2A
T1A
T2A
N1
N2
N1
N2
F1
F2
F4
F3
U
TILITY 1
U
TILITY 2
LO
AD 1
LO
AD 2
23
19
4
194
N1
N2
T1
T2
23
Содержание 4721
Страница 60: ...PART 3 Page 56 V TYPE PREPACKAGED TRANSFER SWITCHES SECTION 3 4 DIAGNOSTIC TESTS...
Страница 98: ...PART 4 Page 94 DC CONTROL LIQUID COOLED ENGINE UNITS SECTION 4 4 DIAGNOSTIC TESTS...
Страница 108: ...Page 104 PART 9 ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE DRAWING 0F0015 A 1 of 2...
Страница 109: ...ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE PART 9 Page 105 DRAWING 0F0015 A 2 of 2...
Страница 112: ...PART 9 Page 108 ELECTRICAL DATA WIRING DIAGRAM 1 5 LITER LIQUID COOLED ENGINE DRAWING 0E0343 B...
Страница 115: ......