UTILITY SOURCE VOLTAGE AVAILABLE
Figure 1 is a schematic representation of the transfer switch with utility source power available. The circuit condi-
tion may be briefly described as follows:
• Utility source voltage is available to Terminal Lugs N1 and N2 of the transfer mechanism.
• Line N2A is closed to the utility closing coil (C1), via a bridge rectifier.
• Utility source voltage is available to limit switch (XA1) via the normally-closed transfer relay contacts (1 and 7)
and Wire No. 126. However, XA1 is open and the Circuit to the utility closing coil is open.
• Utility voltage “sensing” signals are delivered to a control board on the generator, via Wire No. N1A, a 5 amp
fuse (F1), transfer switch terminal N1, to the sensing transformer. The second line of the utility voltage “sens-
ing” circuit is via Wire No. N2A, a 5 amp Fuse (F2), transfer switch terminal N2, to the sensing transformer.
NOTE: Transfer switch terminals N1 and N2 (Utility 1 and 2) must be properly connected to generator ter-
minals N1 and N2 (Utility 1 and 2) by the installer.
TR
RELAY, TRANSFER
TERMINAL STRIP (CUSTOMER CONNECTION)
NB - NEUTRAL BLOCK
LIMIT SWITCHES, ACTUATOR
VARISTOR
FUSE, 5A
VR1,VR2
F1,2,3 & 4
XA1,XB1
NB
TB
TR
194
TB6
TB7
194
23
23
B
TR
A
A
B
B
A
126
1
E1
N2A
*
- NOT USED WITH PREPACKAGED
STANDBY GENERATORS
TRANSFER SWITCH CONTACTOR
SOLENOID COIL (STANDBY CLOSING)
SOLENOID COIL (UTILITY CLOSING)
LEGEND
TR
ATS
C1
C2
N2A
NB
205
6
9
E2
00
T2A
T1A
E2
F4
LOAD 2
UTILITY 2
NEUTRAL
*
(OPTIONAL)
F2
TB2
TB5
TB4
N2
T2
LOAD 1
F3
TB3
T1
ATS
N1A
N1A
7
E1
N2A
UTILITY 1
— SUPPLY INPUT TO
CONTROL
BOARD
— SUPPLY INPUT TO
CONTROL
BOARD
— LOAD INPUT TO
CONTROL
BOARD
— LOAD INPUT TO
CONTROL
BOARD
F1
TB1
N1
NO
XA1
COM
C1
VR1
COM
XB1
NO
NC
NC
C2
VR2
= 12 VDC ALWAYS PRESENT
= AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
FROM
GENERATOR
UTILITY SOURCE
N1
E1
E2
N2
T1
T2
LOAD
Figure 1. Circuit Condition- Utility Source Voltage Available
PART 3
Page 44
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
SECTION 3.2
OPERATIONAL ANALYSIS
Содержание 4721
Страница 60: ...PART 3 Page 56 V TYPE PREPACKAGED TRANSFER SWITCHES SECTION 3 4 DIAGNOSTIC TESTS...
Страница 98: ...PART 4 Page 94 DC CONTROL LIQUID COOLED ENGINE UNITS SECTION 4 4 DIAGNOSTIC TESTS...
Страница 108: ...Page 104 PART 9 ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE DRAWING 0F0015 A 1 of 2...
Страница 109: ...ELECTRICAL DATA V TYPE TRANSFER SWITCH 100 200 AMP 2 POLE PART 9 Page 105 DRAWING 0F0015 A 2 of 2...
Страница 112: ...PART 9 Page 108 ELECTRICAL DATA WIRING DIAGRAM 1 5 LITER LIQUID COOLED ENGINE DRAWING 0E0343 B...
Страница 115: ......