10
ADICOS HOTSPOT-1000
410-2410-001 EN12
INSTALLATION
5 Installation
WARNING!
Incorrect installation of ADICOS detectors can cause malfunctioning, leading to
failure of the fire detection system.
• Only properly trained personnel may perform installation work.
5.1 Requirements of Mounting Location
DANGER!
Standard model ADICOS HOTSPOTs may
not
be installed in
potentially explo-
sive areas
! There are special HOTSPOT models available for use in potentially
explosive areas.
WARNING!
The correct position and direction of the ADICOS HOTSPOT-1000 are essential
to proper and reliable detection. If the device is not placed correctly, the detec-
tor could be completely ineffective!
5.1.1
Protective Measures
To ensure failure-free operation of the ADICOS HOTSPOT-1000, always consider the following
factors when choosing a place to attach the device.
Temperature
Even under the most unfavorable conditions, the ambient temperature at the mounting loca-
tion must remain within the temperature range specified for the ADICOS HOTSPOT-1000 (Re-
fer to Chap. „10 Technical Data“).
Dirt and condensation
The ADICOS HOTSPOT-1000 is equipped with a purge air connection that prevents dusty air
from polluting the optics. A detector heater is needed when there is a risk of condensation
forming on the device.
Moisture
When choosing a place to attach the ADICOS HOTSPOT-1000, take into consideration that it
may not be exposed to moisture. Keep in mind that water could be used for cleaning purposes
near the mounting location.
Vibration
The electronics contained in the ADICOS HOTSPOT-1000 can be damaged when subjected to
vibration. If there are any sources of strong vibration near where the ADICOS HOTSPOT-1000
is mounted, the detector has to be positioned such that its operation is not affected.