INSTALLATION
13
ADICOS HOTSPOT-1000
410-2410-001 EN12
5.2 Mounting
WARNING!
ADICOS HOTSPOT-1000 detectors have to be installed with the enclosure
closed. Do not open the enclosure!
1
Select a suitable mounting location.
2
Install the GTE connection box near the ADICOS HOTSPOT-1000.
3
If applicable, use a 4 mm hose to connect the ADICOS HOTSPOT-1000 to a purge air
supply. This prevents residue from forming on the ADICOS HOTSPOT-1000 optics.
4
Connect the components to one another (Refer to chapter 5.3).
5
Connect the components to the supply voltage.
5.2.1
Installation Requirements
The most important requirement for properly detecting a heat source is that the detector must
have a clear, unobstructed view of the equipment parts and/or objects to be monitored within
the detection area.
Before mounting the device, determine the detection area of a single detector, or adjust it as a
factor of the installation location. When doing this, take into consideration the mounting angle
of the detector as well as the angle of detection.
5.2.2 Mounting the ADICOS HOTSPOT-1000
NOTE!
The ADICOS HOTSPOT-1000 may be installed only by properly trained person-
nel.
Attaching to a mounting plate
The aluminum enclosure of the ADICOS HOTSPOT-1000 has four mounting bores with a thread
cut of M5 in the lower part. These mounting bores/threads can be used to mount the detec-
tor directly or to attach it to a mounting plate. A standard mounting plate is available as an
accessory.
The person installing the device must verify that the mounting plate is positioned such that the
object to be monitored is within the detection area of the ADICOS HOTSPOT-1000.