FUNCTIONING
9
ADICOS HOTSPOT-1000
410-2410-001 EN12
Standard configuration
In the standard configuration, the temperature threshold of the ADICOS HOTSPOT-1000 is
set to 60 °C.
Individual modifications to configuration
The ADICOS service software can be used to change the limit of the ADICOS HOTSPOT-1000
irrespective of the standard (default) configuration upon delivery.
4.2 LED Signals
The current state of the ADICOS HOTSPOT-1000 is indicated by three LEDs.
The following table explains the respective illumination.
LED
State
Functioning
Green
Flashing
Initialization / not yet able to trigger an alarm
On
Normal operation
Off
Detector switched off, no supply voltage available,
fuse or cable defective
Yellow
On
Malfunction mode
Off
Normal mode
With fire panel interface:
Red
Flashing
alarm, but without indication at the fire panel
On
alarm, acknowledged by fire panel
Off
Normal mode
With pre-alarm module:
Red
Flashing
Pre-alarm
On
Alarm
Off
Normal operation
Without fire panel interface:
Red
On
Alarm
Off
Normal operation