8
ADICOS HOTSPOT-1000
410-2410-001 EN12
FUNCTIONING
3.5 Signal Relays
The ADICOS HOTSPOT-1000 has two signal relays to indicate the detector status: one for
the “Alarm” and one for the “Failure” status. The “Alarm” relay is a make contact (NO) and the
“Failure” relay is a break contact (NC). The signal lines for the relays are integrated into the
ADICOS connection cable.
3.6 Detector Heater
The ADICOS HOTSPOT-1000 is equipped with an internal heater. It prevents from condensa-
tion caused by ambient conditions. The heater can be activated or deactivated with aid of the
ADICOS service software. It has a power consumption of up to 10VA. The default condition of
the heating as supplied is inactive.
The heater switches off automatically when under voltage occurs. When the under voltage has
been remedied, the detector heater is not activated again until the ADICOS HOTSPOT-1000
has been reset.
The enclosure temperature is monitored to limit the heating function. If the default tempera-
ture limit of 40 °C is exceeded, the detector heater switches off automatically. The limit may
need to be adjusted in the event of a high ambient temperature along with high humidity.
3.7 ADICOS M-Bus
The ADICOS M-Bus is a two-wire data line used to transmit all of the detector parameters as
well as the operating and measurement data to the ADICOS M-Bus Interface (ADICOS M-BUS-
MASTER XF or S) used. These data can be displayed and archived using the ADICOS service
software. The parameters for all of the connected detectors can be set via the ADICOS M-Bus
as well. The M-Bus lines are integrated into the ADICOS connection cable.
4 Functioning
When the ADICOS HOTSPOT-1000 is in operation, it triggers an alarm according to the set
threshold combinations. With aid of the ADICOS M-Bus interface (M-BUSMASTER XF or S) the
detector the detector also transmits all sensor and operating data to the ADICOS service soft-
ware to be displayed.
If the ADICOS HOTSPOT-1000 is connected to a fire panel with aid of an internal interface
module, the fire panel controls the detector’s alarm display.
4.1 Configuration and Evaluation
One of the outstanding feature of the ADICOS HOTSPOT-1000 is its capacity to early detect
hot spots based on programmable parameters. The field of view of the HOTSPOT is divided
into 4 x 4 segments. An individual alarm threshold can be set for each segment. Each detector
has two sets of limit values. In addition to temperatures, the detectors also detect flames.