15.3 Pump
Shaft seal
Mechanical shaft seals are maintenance-free and almost leak-
free. In case of considerable and increasing leakage, check the
shaft seal immediately. If the seal faces are damaged, replace the
entire shaft seal. See service instructions for the pump and
section
.
Bearings
In the pump maintenance-free, permanently lubricated bearings
are installed.
15.4 Diesel engine
Check the fuel level in fuel tank and add fuel, if necessary.
Check the pipes of the fuel system for leakages.
Replace defective fuel pipes and tighten loose pipe connections.
Fasten the fuel pipes with Norma type torque brackets.
Drain condensate from the fuel tank and the fuel filter.
Check oil level and add oil, if necessary.
Water-cooled diesel engines:
Check the level of cooling liquid in the equalisation tank and add
cooling liquid, if necessary.
• Water-cooled diesel engines: Check pipes and hoses of the
cooling system for leakages. Replace defective pipes and
hoses. Tighten loose pipe and hose connections.
• Check if the pressure gauge of the cooling circuit, if any,
displays a pressure value when the engine is running.
• Check the entire exhaust pipe system for leaks while the
engine is running. Tighten loose pipe connections and replace
defective pipes immediately.
• Check V-belts for wear and correct tension.
• Check air filter.
15.5 Electric motor
Check the electric motor visually once a week. Keep the motor
clean to ensure adequate ventilation.
Electric motors up to and including size 160 have maintenance-
free, permanently lubricated bearings. Electric motors bigger than
size 160 are to be lubricated according to the data on the
nameplate. Note that excess lubricant can be released from the
motor.
Use lithium-based grease according to these specifications:
• NLGI grade 2 or 3.
• Viscosity of basic oil: 70 to 150 cSt at +40 °C.
• Temperature range: -30 °C to +140 °C.
15.6 Coupling
Couplings used for pump sets are maintenance-free. However,
check the alignment of the pump and driver once a year.
See section
15.7 Controller
Note
See also installation and operating instructions
for the diesel engine.
Warning
During and after operation, surfaces,
components and working materials of the diesel
engine can be very hot.
Warning
Fuel vapours are flammable. Therefore, never top
up fuel when the engine is running or when the
engine is warm.
Do not inhale fuel vapours when filling the fuel
tank.
Ensure good ventilation of the room during the
refuelling so that the fuel vapours are dissipated
quickly.
Do not start the engine when there are fuel
vapours in the room.
Caution
Use the diesel fuel specified by the manufacturer
of the diesel engine.
Note
Collect water-containing and excess fuel in a
suitable vessel and dispose of it in accordance
with local regulations.
Caution
Do not fill oil above the maximum mark.
Overfilling may damage the engine.
Use only the type of oil specified by the
manufacturer of the diesel engine.
Warning
Do not the remove cap of equalisation tank when
the engine is warm. The tank is under pressure.
Caution
Use only the type of cooling liquid specified by
the manufacturer of the diesel engine.
Warning
A damaged exhaust gas system may result in
suffocation.
Note
See also installation and operating instructions
for the electric motor.
Note
See installation and operating instructions for
the controller.
Содержание Fire NKF
Страница 1: ...GRUNDFOS INSTRUCTIONS Fire NKF Installation and operating instructions...
Страница 31: ...English GB 31...
Страница 259: ...BG 33 4 NKF Grundfos Fire NKF 5 5 1 5 1 1 1 5 1 2 5 2 5 2 1 2 5 2 2 Grundfos TM03 2932 4905 2 TM03 7770 4906...
Страница 267: ...BG 41 9 7 9 8 120 C 9 9 9 10 10 10 1 10 2 1 5 10 100 mm 10 Fire NKF TM05 2546 0212...
Страница 272: ...BG 46 10 6 19 19 20 20 10 7 10 8 9 4 10 9 A B C 21 21 8 1 10 9 12 1 TM00 2263 3393 TM03 7775 4906 TM04 0113 5007 A B C...
Страница 274: ...BG 48 10 11 26 26 27 SUPPLY RETURN 27 10 12 Flex 11 TM04 9851 0211 TM04 5069 2609 A...
Страница 276: ...BG 50 1 2 3 4 5 28 25 Nm 1 2 30 Nm 3 8 6 7 8 12 3 12 4 16...
Страница 277: ...BG 51 13 16 6 14 1 2 3 29 25 Nm 1 2 30 Nm 3 8 29 5 1 2 1 2 12 TM03 3935 1206...
Страница 278: ...BG 52 15 15 1 x x x x x x x x x x x x x V x V x x x x x x x x x x...
Страница 279: ...BG 53 15 2 10 5 13 15 3 12 4 15 4 Norma V 15 5 160 160 NLGI 2 3 70 150 cSt 40 C 30 C 140 C 15 6 10 5 15 7...
Страница 280: ...BG 54 16 16 1 1 a b c d e 9 2 10 6 f g 2 a b c d 3 a 9 2 10 6 b c d e f g h i j 4 a b c d e...
Страница 281: ...BG 55 16 2 5 a b 9 2 10 6 c d 10 5 e f g 1 a 10 6 b c d 9 2 e 2 a 9 2 b 10 6 c d e 10 6 f g h 3 a 10 6 b 4 a b c...
Страница 282: ...BG 56 5 a b 9 2 c d 10 6 10 5 e 6 a b c d e f g h i 7 a b c d Grundfos 8 a b c Grundfos 9 a Grundfos b c d e Grundfos...
Страница 283: ...BG 57 17 Grundfos Grundfos Grundfos 7 18 19 20 1 2 Grundfos 10 a b c d V V e Grundfos 11 a Grundfos Grundfos...
Страница 386: ...Appendix 385 Appendix 1 Exploded view of fire pump TM03 1508 2305...