English (GB)
14
8.2 Pump set
Weight: See nameplate.
Sound pressure level
9. Operating conditions
9.1 Maximum operating pressure
NKF pumps are designed for a maximum operating pressure of
16 bar.
9.2 Minimum inlet pressure
The minimum inlet pressure "H" in metres head required at the
suction port of the pump during operation to avoid cavitation in
the pump can be calculated from the following formula:
H = p
b
x 10.2 - NPSH - H
f
- H
v
- H
s
If the calculated value of "H" is positive, the pump can operate
with a maximum suction lift of "H" metres.
If the calculated value of "H" is negative, a minimum suction head
of "H" metres is required.
Relation between vapour pressure and liquid temperature t
m
Fig. 9
Vapour pressure scale
9.3 Maximum inlet pressure
The actual inlet pr closed-valve pressure must always be
lower than the maximum operating pressure.
See section
9.1 Maximum operating pressure
The closed-valve pressure of the pump can be taken from the
data booklet of the pump set.
9.4 Minimum flow rate
In pumps with water-cooled diesel engine, a minimum flow rate is
ensured by a pipe connecting the discharge port with the heat
exchanger.
Pumps with electric motor and air-cooled diesel engine must be
fitted with a bypass pipe to ensure a minimum flow rate of 2 %
(5 % for NKF 125-315) of the flow rate at maximum efficiency.
The minimum flow rate will help to lead away excess heat and
thus protect the pump against overheating.
Note
See technical data in the installation and
operating instructions for the controller and
driver.
Note
The sound pressure level depends on the driver.
Note
Pump set with diesel engine:
The silencer supplied is designed for the
requirements of the industrial market. If you have
stricter noise level requirements, you can order
and install another silencer.
Note
NKF pumps with VdS approval:
To comply with VdS requirements, the pump
head must not exceed 120 metres (12 bar).
p
b
Barometric pressure in bar.
(The barometric pressure can be taken as = 1 bar.)
In closed systems, p
b
is equal to the system pressure in
bar.
NPSH
Net Positive Suction Head in metres head (to be read
from the NPSH curve at the highest flow the pump will
be delivering).
It can be read from the curves in the data booklet.
H
f
Friction loss in suction pipe in metres head.
H
v
Vapour pressure in metres head,
with t
m
= liquid temperature (see fig. 9).
H
s
NKF pumps according to EN and DBI:
Safety margin = minimum 0.5 metres head.
NKF pumps according to VdS CEA 4001:2010-11 (04):
Safety margin = minimum 1 metre head.
TM
00 30
37 07
98
Caution
Warning
The pump must not run against a closed valve as
this may cause an unacceptable temperature
increase or formation of vapour.
20
15
12
10
8,0
6,0
5,0
4,0
3,0
2,0
1,0
0,8
0,6
0,4
0,3
0,2
0,1
1,5
120
110
90
100
80
70
60
50
40
30
20
10
0
Hv
(m)
tm
(°C)
150
130
140
25
35
45
40
30
Содержание Fire NKF
Страница 1: ...GRUNDFOS INSTRUCTIONS Fire NKF Installation and operating instructions...
Страница 31: ...English GB 31...
Страница 259: ...BG 33 4 NKF Grundfos Fire NKF 5 5 1 5 1 1 1 5 1 2 5 2 5 2 1 2 5 2 2 Grundfos TM03 2932 4905 2 TM03 7770 4906...
Страница 267: ...BG 41 9 7 9 8 120 C 9 9 9 10 10 10 1 10 2 1 5 10 100 mm 10 Fire NKF TM05 2546 0212...
Страница 272: ...BG 46 10 6 19 19 20 20 10 7 10 8 9 4 10 9 A B C 21 21 8 1 10 9 12 1 TM00 2263 3393 TM03 7775 4906 TM04 0113 5007 A B C...
Страница 274: ...BG 48 10 11 26 26 27 SUPPLY RETURN 27 10 12 Flex 11 TM04 9851 0211 TM04 5069 2609 A...
Страница 276: ...BG 50 1 2 3 4 5 28 25 Nm 1 2 30 Nm 3 8 6 7 8 12 3 12 4 16...
Страница 277: ...BG 51 13 16 6 14 1 2 3 29 25 Nm 1 2 30 Nm 3 8 29 5 1 2 1 2 12 TM03 3935 1206...
Страница 278: ...BG 52 15 15 1 x x x x x x x x x x x x x V x V x x x x x x x x x x...
Страница 279: ...BG 53 15 2 10 5 13 15 3 12 4 15 4 Norma V 15 5 160 160 NLGI 2 3 70 150 cSt 40 C 30 C 140 C 15 6 10 5 15 7...
Страница 280: ...BG 54 16 16 1 1 a b c d e 9 2 10 6 f g 2 a b c d 3 a 9 2 10 6 b c d e f g h i j 4 a b c d e...
Страница 281: ...BG 55 16 2 5 a b 9 2 10 6 c d 10 5 e f g 1 a 10 6 b c d 9 2 e 2 a 9 2 b 10 6 c d e 10 6 f g h 3 a 10 6 b 4 a b c...
Страница 282: ...BG 56 5 a b 9 2 c d 10 6 10 5 e 6 a b c d e f g h i 7 a b c d Grundfos 8 a b c Grundfos 9 a Grundfos b c d e Grundfos...
Страница 283: ...BG 57 17 Grundfos Grundfos Grundfos 7 18 19 20 1 2 Grundfos 10 a b c d V V e Grundfos 11 a Grundfos Grundfos...
Страница 386: ...Appendix 385 Appendix 1 Exploded view of fire pump TM03 1508 2305...