Index Parameter
unit
Factory-
setting
Setting
range
Remarks
0
Function of pro-
grammable output
(voltage-free relay
contact) SA
SA 1
SA 0 ... SA 4 0 = collective fault alarm active (contact is
open in case of power failure or
when a malfunction occurs).
1 = contact is only closed in case of mal-
function.
2 = activation of a delivery pump for re-
generation water (order no. 188
800).
3 = closed during the entire regeneration
process
4 = contact closed in case of a flow rate
of 0 m³/h or in case of transfer.
1
Delay time for SA
= 4 [min.]
1,0
0,1 … 9,9
Contact only reopens time-delayed when
the transfer has been completed.
2
Dosing interface
EXAcount IA
IA 2
IA 0 … IA 3 0 = pulse output 1:1
1 = pulse output 1:10
2 = pulse output 1:1
3 = pulse output 1:10
When 2 or 3 is set, no EXADOS
®
dosing
will take place as long as an error,
Er1/2/4/6/7, is pending at the Weichwas-
sermeister
®
GSX and therefore, no soft
water is available.
3
Function of pro-
grammable input
(to connect to
voltage-free con-
tact provided by
others)
0
0 ... 3
0 = no function
1 = external release of regeneration
2 = external lock of regeneration
3 = reserved function
Table F-4: Parameters of Installer level 113