Water Softener
Weichwassermeister
®
GSX 5, GSX 10, GSX 10-I
Order no. 075 187 970-inter Edited by: KONS-nkes-mrie G:\BA-187970-INTER_GSX 5-10.DOC
23
Provide a drain connection (at least DN 50) to discharge the regenera-
tion water.
The installation site must have a floor drain. If this is not the case, an
appropriate water stop device must be installed (refer to chapter C,
paragraph 6.2).
Note:
If the regeneration water is directed into a lifting device, this de-
vice must be salt water resistant.
Attention!
A non-return valve is installed on the inlet side of the con-
nection block (fig. C-2, item 5). Pressure relief safety valves therefore
must be installed downstream of the connection block.
1.2 Electrical
installation
An earthed socket is required for the electrical connection. It must cor-
respond to the specifications in table C-1 and must be no further from
the water softener than 1.20 m.
Attention!
The socket must carry constant voltage (do not couple with
light switch or emergency switch of heating system).
2 | Preliminary work
1.
Unpack all components of the water softener.
2.
Check for completeness and soundness.
3.
Place the system at the designated location.
3 | How to connect the system
3.1 Water connection
Install connection block into the piping (pay attention to sieve insert)
Mount connection hoses (observe flow direction).
Fig. D-2: Water connection of Weichwassermeister
®
GSX