47
309085
Dual Ram Cross-Over Control Function
Dedicate Zones
To dedicate zones, access the SETUP screens by
pressing F5 from the MAIN menu, enter the correct
password, acknowledge the proper zones are config-
ured and proceed to the following screen.
5 = C R O S S – O V E R
C O N F I G
6 =
7 = 7
D A Y
T I M E R
B A C K
N E X T
F1
F2
F3
F4
F5
Press 5 on the numeric keypad to access the Cross-
Over Configuration screen.
A = D E D I C A T E
Z O N E S
B = F A C T O R Y
S E T U P
( G r a c o
u s e
o n l y ! )
o n
E X I T
F1
F2
F3
F4
F5
There are two options available in the Cross-Over
Configuration screen. DEDICATE ZONES to a partic-
ular unloader or FACTORY SETUP. FACTORY SET-
UP will be discussed later. Press A on the keypad to
access the DEDICATE ZONES screen as shown
below.
> A L W A Y S
O N <
Z O N E # 0 1
N A M E : G U N
# 1
A C T I V E
Z N –
C H G
E X I T
O N
Z N +
F1
F2
F3
F4
F5
The DEDICATE ZONES screen shows the ZONE #
and zone NAME, the ACTIVE or UNUSED status of
the zone and whether the zone is ALWAYS ON or
dedicated to UNLOADER A or UNLOADER B. Press-
ing the F1(ZN–) and F5 (ZN+) will toggle through the
zones. Pressing F2 (CHG) will change the dedication
status shown from ALWAYS ON, to UNLOADER A or
UNLOADER B. Ensure the proper dedication status is
entered for each zones. For zones that are UNUSED,
leave as ALWAYS ON dedication status. The pendant
will ignore that zone if it is UNUSED.
Return back to the main screen. At this point the
X-Over system is ready to run.
Содержание Therm-O-Flow Plus
Страница 22: ...22 309085 Notes...
Страница 28: ...28 309085 Advanced Pendant Control Screen Map TI0683 See Next Page...
Страница 30: ...30 309085 Notes...
Страница 43: ...43 309085 Notes...
Страница 60: ...60 309085 Service For 400 480 and 575 VAC Supply Units Junction Box Schematic Fig 18 TI0673...
Страница 61: ...61 309085 Service For 240 VAC Supply Units Junction Box Schematic Fig 19 TI0673...
Страница 65: ...65 309085 Notes...