Installation
Ground The System
Ground the supply unit as instructed here and in the
individual component manuals.
WARNING
FIRE, EXPLOSION, AND ELECTRIC
SHOCK HAZARD
To reduce the risk of fire, explosion, or
electric shock:
The power source conduit is not an
adequate ground for the system. The
unit must be bonded to either the
building ground or a true earth
ground.
A qualified electrician must complete
all grounding and wiring connections
and check the resistance as
instructed on page 15.
Refer to your local code for the requirements for
a “true earth ground” in your area.
Also read and follow the warnings on page 5.
To reduce the risk of static sparking, ground the pump,
object being dispensed to, and all other spraying/dis-
pensing equipment used or located in the spraying/dis-
pensing area. Check your local electrical code for
detailed grounding instructions for your area and type
of equipment.
Air and Fluid Hoses:
Use only electrically conductive hoses.
Dispensing/Spray Gun
Follow the dispensing/spray gun grounding instruc-
tions.
Object Material is Applied To
Ground the object according to your local code.
Material Drums
Ground the material drums according to your local
code. Use only metal drums placed on a grounded
surface. Do not place the drum on a nonconductive
surface, such as paper or cardboard, which interrupts
the grounding continuity.
Maintain Grounding Continuity When Purging Or
Relieving Pressure
Follow the instructions in your separate gun manual for
safely grounding your gun while purging.
Содержание Therm-O-Flow Plus
Страница 22: ...22 309085 Notes...
Страница 28: ...28 309085 Advanced Pendant Control Screen Map TI0683 See Next Page...
Страница 30: ...30 309085 Notes...
Страница 43: ...43 309085 Notes...
Страница 60: ...60 309085 Service For 400 480 and 575 VAC Supply Units Junction Box Schematic Fig 18 TI0673...
Страница 61: ...61 309085 Service For 240 VAC Supply Units Junction Box Schematic Fig 19 TI0673...
Страница 65: ...65 309085 Notes...