26
309085
Operation
Reading the Temperature Controllers
Refer to Form 309100 for instructions on reading the
CB100 temperature controller.
Temperature Out of Range
Should any of the temperatures go out of the preset
range for any of the zones, power to the heated com-
ponents is interrupted, and the HIGH TEMPERA-
TURE ALARM light (AD) goes ON. The alarm auto-
matically goes OFF and the system resets when the
temperature is back in range. The HIGH TEMPERA-
TURE ALARM will activate at 40
F (22
C) over the set
value (SV).
Within limits
(green READY light on)
HIGH TEMP
ALARM
SV
35
F (19
C)
below the SV
40
F (22
C)
above the SV
The green READY light will illuminate when the tem-
perature is within the limits of 35
F (19
C) below the
SV to 40
F (22
C) above the SV. The green READY
light also indicates that the air solenoid is allowed to
operate.
Resetting the Supply Unit After the Inactivity T imer
(Worklife Timer) Has Been Triggered
Your system may have an inactivity timer. If the pump
has not moved for a set amount of time, the inactivity
timer:
turns off power to the heaters
lights the AUTO HEAT OFF light (AE)
To re-heat the supply unit:
Fig. 10
66
1. Turn the HEAT switch (V) to the OFF position,
then turn it to the ON position.
2. Wait until all components in the supply unit have
returned to operating temperature.
3. Resume operation.
Setting the Optional Inactivity T imer
1. Turn off the main power.
2. Open the control box (Fig. 11).
3. Locate the timer in the left hand column, bottom
row (last item mounted on the right end of the rail).
4. Select a time on dial 1. Default is 1–10 hours.
5. Set mode “2S” on dial 2.
NOTE: The timer must be set to a value larger than
the heat–up time of your system, or the machine will
never reach normal temperature.
Содержание Therm-O-Flow Plus
Страница 22: ...22 309085 Notes...
Страница 28: ...28 309085 Advanced Pendant Control Screen Map TI0683 See Next Page...
Страница 30: ...30 309085 Notes...
Страница 43: ...43 309085 Notes...
Страница 60: ...60 309085 Service For 400 480 and 575 VAC Supply Units Junction Box Schematic Fig 18 TI0673...
Страница 61: ...61 309085 Service For 240 VAC Supply Units Junction Box Schematic Fig 19 TI0673...
Страница 65: ...65 309085 Notes...