English
Clamp Multimeter METRACLIP 86
Resolution
0.1
Ω
1
Ω
10
Ω
Open-circuit voltage
≤
3,6 V
Measurement current
550µA
100µA
10µA
Note (1) - Above the maximum display value, the display unit indicates "OL".
- The "-" and "+" signs are not managed.
Specific characteristics in MAX/MIN mode
:
•
Uncertainties: add 1% R to the values of the table above.
•
Capture time of the extrema: approximately 100ms.
4.2.10 Diode test
Measurement range
0.000V to 3.199V DC
Specified measurement range
1 to 100% of the measurement range
Uncertainties
± (1% R + 3 pt)
Resolution
0.001V
Measurement current
0.55 mA
Indication: junction reversed or
open-circuit
Display of "OL" when the measured
voltage >3.199V
Note : The "-" sign is disabled for the diode test function.
4.2.11 Active DC power measurements
Measurement
range (2)
0 W to
5999 W
6.00 kW
to
59.99 kW
60.0 kW to
599.9 kW
600 kW to
900 kW (1)
Specified
measurement
range
1 to 100% of the
measurement range
0 to 100% of the measurement range
Uncertainties
(3)
± (2% R +10 pt)
± (2% R +3 pt)
Resolution
1W
10W
100W
1,000W
Note (1) - Display of O.L or ± O.L
- Above 900kW in single-phase (1000V x 900A).
- Above ±1800kW, in REL mode.
39