49
Troubleshooting
Problem
Cause
Remedy
The steam trap is cold or only
hand-hot.
The shut-off valves for
condensate inlet or outlet are
closed.
Open the shut-off valves.
The condensate inlet or outlet
is dirt clogged.
Clean the pipes.
Clean the equipment.
The steam trap is blowing off
live steam.
The steam trap is adjusted to
obtain a leak passage
(minimum flowrate).
Adjust the steam trap to give steam-tight
shut-off.
The membrane regulator
capsules are dirty.
There are dirt deposits in the
equipment.
Clean the membrane regulator capsules.
Clean the equipment.
Replace the membrane regulator
capsules with new ones.
The membrane regulator
capsules are worn.
The seat is leaking.
Replace the membrane regulator
capsules with new ones.
The bypass is open.
Close the bypass.
Insufficient condensate
discharge.
Insufficient thermal output of
the user.
The shut-off valves for
condensate inlet or outlet are
closed.
Open the shut-off valves.
The condensate inlet or outlet
is dirt clogged.
Clean the pipes.
Clean the equipment.
Replace the membrane regulator
capsules with new ones.
Steam pressure and
condensate flowrate fluctuate
considerably.
The pressure upstream of the
steam trap is too low for the
used trap type.
Use a different steam trap type.
Contact the manufacturer to find out
which trap type is the most suitable for
your application.
The steam trap is undersized. Use a steam trap with a larger
condensate discharge capacity.
Содержание TK 23
Страница 1: ...Steam Trap for Large Condensate Flowrates TK 23 TK 24 Original Installation Instructions 819309 01 ...
Страница 56: ...56 Capacity Charts Capacity chart for hot water A Flowrate B Differential pressure Δ PMX ...
Страница 57: ...57 Capacity chart for cold water A Flowrate B Differential pressure Δ PMX ...
Страница 62: ...62 ...
Страница 63: ...63 ...