50
Problem
Cause
Remedy
The differential pressure is too
small.
Increase the steam pressure.
Lower the pressure in the condensate
line.
Check the size of the condensate line.
Install a steam trap with a larger
condensate discharge capacity or a
condensate return unit.
The distance between the drain
point and the steam trap is too
small.
Install the uninsulated steam trap approx.
1 - 2 m away from the drain point.
Do not insulate the condensate line and
lay it with a gradient so that the
condensate is free to fall towards the
steam trap.
The condensate line does not
have a slight fall from the drain
point towards the steam trap.
The condensate is lifted
upstream of the steam trap.
Lay the condensate line with a gradient
so that the condensate is free to fall
towards the steam trap.
Change the orientation of the condensate
line.
The steam trap is adjusted to
give steam-tight shut-off.
Restore the factory setting.
If necessary re-adjust the settings of the
steam trap.
The condensate temperature is
higher than the service
temperature of the steam trap.
The regulator does not open or
only with a time delay.
If the steam trap or the condensate line
is insulated remove the insulation.
Use a different steam trap type.
Insufficient deaeration.
Provide additional deaeration.
Use a different steam trap type.
Contact the manufacturer to find out
which trap type is the most suitable for
your application.
Содержание TK 23
Страница 1: ...Steam Trap for Large Condensate Flowrates TK 23 TK 24 Original Installation Instructions 819309 01 ...
Страница 56: ...56 Capacity Charts Capacity chart for hot water A Flowrate B Differential pressure Δ PMX ...
Страница 57: ...57 Capacity chart for cold water A Flowrate B Differential pressure Δ PMX ...
Страница 62: ...62 ...
Страница 63: ...63 ...