13
Adapting settings
To guarantee a rapid response to temperature
changes, the membrane regulator capsules are
permanently exposed to defined partial flow of the
fluid (= minimium flowrate, so-called "leak
passage").
The following default partial flow settings are
adjusted at our factory:
Equipment with DN 50: 2 % of the maximum
flowrate
Equipment with DN 65 - 80: 1.5% of the
maximum flowrate
Equipment with DN 100: 1% of the maximum
flowrate
With factory setting the equipment discharges the
quantities given in the capacity charts on page 56.
To custom fit the steam trap to the individual
operating conditions of your installation you can
adjust the flowrate by limiting the valve travel ("lift
restriction") for the open or closed position.
Equipment with DN 50 is provided with only one
adjustment screw. With this equipment you can
only adjust either a maximum or a minimum
flowrate ("leak passage").
Equipment from DN 65 onwards is provided with
two adjustment screws. Use the adjustment screw
on the top cover to regulate the maximum flowrate.
Use the adjustment screw on the bottom cover to
regulate the minimum flowrate.
DANGER
Personnel working on pipes are exposed to
safety risks and may suffer severe injuries,
poisoning or even loss of life.
Make sure that no hot or hazardous
fluid is in the equipment or the pipes.
Make sure that the pipes upstream
and downstream of the equipment are
depressurised.
Make sure that the installation is
switched off and protected against
unauthorised or unintended activation.
Make sure that the equipment and the
pipes have cooled down to room
temperatures.
Wear protective clothing that is
suitable for the fluid and, if necessary,
wear protective gear.
For more information on suitable protective clothing
and safety gear refer to the safety data sheet of the
fluid in question.
For work on the equipment you will need the
following tools:
Torque spanner (US: wrench) 4-40 Nm
Torque spanner (US: wrench) 20-120 Nm
2 Spanners A. F. 8 mm
2 Spanners A. F. 19 mm (TK 23) or 24 mm (TK
24)
Screwdriver 6 mm
Screwdriver 10 mm
Содержание TK 23
Страница 1: ...Steam Trap for Large Condensate Flowrates TK 23 TK 24 Original Installation Instructions 819309 01 ...
Страница 56: ...56 Capacity Charts Capacity chart for hot water A Flowrate B Differential pressure Δ PMX ...
Страница 57: ...57 Capacity chart for cold water A Flowrate B Differential pressure Δ PMX ...
Страница 62: ...62 ...
Страница 63: ...63 ...