Adjustment to give steam-tight shut-off
To prevent steam loss you can adjust the
equipment to give steam-tight shut-off. To do so
you have to set the minimum flowrate to zero.
Attention!
Malfunctions due to banking-up of
condensate.
Limiting the maximum flowrate changes
the factory-set leak passage ("partial
flow"). The equipment closes as soon as
steam arrives. Note that the
responsiveness of the membrane regulator
is reduced due to the lack of a partial flow.
As a result condensate may bank up.
Make sure that the process in the
higher-level plant system is not
impaired by banking-up of
condensate.
To ensure that the equipment gives steam-tight
shut-off the following work must be performed on
the lower adjustment screw:
Make sure that the equipment is depressurized,
cooled down to room temperature and free from
fluid.
To reduce the pressure through the bore in the
cover slowly loosen the sealing plug by two
turns (10).
Remove the cap nut (1).
Remove the outer gasket (26) from the
adjustment screw.
Remove the hexagon nut (25).
Remove the inner gasket (26) from the
adjustment screw.
Screw out the adjustment screw (12) until a
resistance is felt.