Watchdog 100 Instruction Manual
36
© 2017 Geist
GM1118 Watchdog 100 Instruction Manual
Figure 3-10 Target Page
·
Delay:
determines how long this Event must remain tripped for before this Action's first
notification is sent. This is different from the Trip Delay above. Trip Delay determines
how long the threshold value has to be exceeded before the Event itself is tripped. This
delay determines how long the Event must remain tripped before this Action occurs.
Delay can be up to 14400 seconds (4 hours). A Delay of 0 will send the notification
immediately.
·
Repeat:
determines whether multiple notifications will be sent for this Event Action.
Repeat notifications are sent at the specified intervals until the Event is acknowledged,
or until the Event is cleared and reset. The Repeat interval can be up to 14400 seconds
(4 hours). A Repeat of 0 disables this feature, and only one notification will be sent.
Then, click
Save
to save this notification Action.
More than one Action can be set for an Alarm or Warning; to add multiple Actions, just
click the Add icon again and set each one as desired. Each alert can have up to 32
Actions associated with it.
To change an existing Alarm or Warning Event:
Click the
Modify
icon next to the Alarm or Warning Event you wish to change, then modify
the specific settings as shown.