Watchdog 100 Instruction Manual
16
© 2017 Geist
GM1118 Watchdog 100 Instruction Manual
Environmental
The operational environmental limits pertaining to Temperature, Humidity and
Elevation are as defined below.
Temperature
Table 1-1
Temperature Limits
Minimum
Maximum
Operating
-10°C (50°F)
45°C (104°F)
Storage
-25°C (-13°F)
65°C (149°F)
Humidity
Table 1-2
Humidity Limits
Minimum
Maximum
Operating
5%
95% (non-condensing)
Storage
5%
95% (non-condensing)
Elevation
Table 1-3
Elevation Limits
Minimum
Maximum
Operating
0 m (0 ft)
2,000 m (6,561 ft)
Storage
0 m (0 ft)
15,240 m (50,000 ft)
Electrical
6-12 Volts DC, 2 Amps
Power-Over-Ethernet (PoE) Enabled (Class 0)
Output Relay Contact Ratings
The output relay contacts are intended to carry low voltage signals only. Do not
exceed the following ratings on the output relay contacts:
DC: 60V, 30W
AC: 30Vrms, 1A