ADV100 • Functions description and parameters list
When set to
0
(
Open loop
) the slip compensation value is that set manually in parameter 5210 or calculated by the
self-tuning procedure.
If set to
1 (Closed loop
) the slip compensation value is measured by the reading of the signals by a digital encoder
keyed to the motor shaft. The EXP-DE-I1R1F1-ADV expansion card must be installed in the drive in order to acquire
encoder signals.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
21.13 2446 Slip P gain
perc FLOAT
1.0
0.0
100.0
ERWS V
Setting of the slip compensation proportional gain.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
21.14 2448 Slip I gain
perc FLOAT
1.5
0.0
100.0
ERWS V
Setting of the slip compensation integral gain.
Vf limit
Torque lim Pos Inuse
PAR 2360
Torque lim Neg Inuse
PAR 2362
Torque curr lim Pos
PAR 2350
Torque curr lim Neg
PAR 2352
Torque curr lim sel
PAR 2354
Vfcurrent lim I time
PAR 2362
Vfcurrent lim P time
PAR 2460
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
21.15 2460 Vfcurrent lim P gain
Hz/A FLOAT
CALCF
0.0
1000.0
ERWS V
Setting of the proportional gain limit in V/f mode. This is calculated automatically if the self-tuning procedure is per-
formed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
21.16 2462 Vfcurrent lim I time
ms
FLOAT
CALCF
1.0
50.0
ERWS V
Setting of the proportional gain limit in V/f mode. This is calculated automatically if the self-tuning procedure is per-
formed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
21.17 2470 Damping gain
perc UINT16
0
0
100
ERW V
Setting of the damping gain. The parameter is used to eliminate any oscillations or faults in the drive output current,
deriving from configurations capable of generating oscillations in the drive/cable/motor system. If oscillations occur,
gradually increase the value of this parameter, until they disappear.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
21.18 2472 Damping threshold 1
Hz
INT16
20
5
100
ERW V
Setting of the first damping gain regulation threshold. These settings are usually effective for intermediate frequen-
cies and make it possible to limit motor oscillations.
Содержание SIEIDrive ADV100
Страница 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Страница 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Страница 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Страница 153: ...ADV100 Block Diagrams 153 References ...
Страница 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Страница 155: ...ADV100 Block Diagrams 155 Multireference ...
Страница 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Страница 157: ...ADV100 Block Diagrams 157 Monitor function ...
Страница 158: ...158 ADV100 Block Diagrams ...
Страница 159: ...ADV100 Block Diagrams 159 Commands ...
Страница 160: ...160 ADV100 Block Diagrams ...
Страница 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Страница 162: ...162 ADV100 Block Diagrams Analog inputs ...
Страница 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Страница 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Страница 165: ...ADV100 Block Diagrams 165 Torque config ...
Страница 166: ...166 ADV100 Block Diagrams VF parameters ...
Страница 167: ...ADV100 Block Diagrams 167 Functions ...
Страница 168: ...168 ADV100 Block Diagrams ...
Страница 169: ...ADV100 Block Diagrams 169 ...
Страница 170: ...170 ADV100 Block Diagrams PID application ...
Страница 171: ......