ADV100 • Functions description and parameters list
125
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11010 Refences unit
ENUM
%
0
3
RWZ FVS
Parameter for selecting the unit of measure of the value to be controlled. It changes the unit of measure in param-
eters 11002
Set point val
, 11006
Feedback val
, 11012
Signals full scale
and 11014
Signals offset
.
0
%
1
m3/h
2
°C
3
bar
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11012 Signals full scale
FLOAT
100
RWZ FVS
Parameter for scaling the input reference and feedback. It must correspond to the maximum limit for the value to be
controlled.
For correct tuning, for example when a transducer is used to measure the feedback that supplies a 0-10V signal.
The recommended setting for this parameter is the physical value to which the 10V of the signal correspond. (e.g. 5
bar = 10V)
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11014 Signals offset
FLOAT
0
RWZ FVS
Parameter for scaling the input reference and feedback. This must correspond to the minimum limit for the value to
be controlled.
For correct tuning, for example when a transducer is used to measure the feedback that supplies a 0-10V signal.
The recommended setting for this parameter is the physical value to which the 0V of the signal correspond.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11016 Start PID sel
ENUM
Mon ing an 1X 0
4484
RW FVS
Parameter for selecting the source of the command to enable the PID controller. If this command is not active when
the PID is enabled, the PID will be in the STOP condition, the PID controller will not function and the drive will be
disabled.
When
Digital Param
[0] is selected the source of the Start PID command corresponds to the value set in parameter
11018
Start PID
.
0
Digital Param
1110
Dig Inp E Mon
1210
Dig Input 1X
1212
Dig Input 2X
1214
Dig Input 3X
1216
Dig Input 4X
1218
Dig Input 5X
1220
Dig Input 6X
1222
Dig Input 7X
1224
Dig Input 8x
3702
PID Start mon
3704
FB level alarm
3706
Wait state mon
3708
Const pres mon
3710
Pad 6
3712
Pad 7
3714
Pad 8
3716
Pad 9
3718
Pad 10
3720
Pad 11
3722
Pad 12
3724
Pad 13
3726
Pad 14
3728
Pad 15
3730
Pad 16
4024
FieldbusM->S1
4034
FieldbusM->S2
Содержание SIEIDrive ADV100
Страница 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Страница 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Страница 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Страница 153: ...ADV100 Block Diagrams 153 References ...
Страница 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Страница 155: ...ADV100 Block Diagrams 155 Multireference ...
Страница 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Страница 157: ...ADV100 Block Diagrams 157 Monitor function ...
Страница 158: ...158 ADV100 Block Diagrams ...
Страница 159: ...ADV100 Block Diagrams 159 Commands ...
Страница 160: ...160 ADV100 Block Diagrams ...
Страница 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Страница 162: ...162 ADV100 Block Diagrams Analog inputs ...
Страница 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Страница 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Страница 165: ...ADV100 Block Diagrams 165 Torque config ...
Страница 166: ...166 ADV100 Block Diagrams VF parameters ...
Страница 167: ...ADV100 Block Diagrams 167 Functions ...
Страница 168: ...168 ADV100 Block Diagrams ...
Страница 169: ...ADV100 Block Diagrams 169 ...
Страница 170: ...170 ADV100 Block Diagrams PID application ...
Страница 171: ......