ADV100 • Functions description and parameters list
115
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.5
4508 ExtFlt restart time
ms
UINT16
1000
120
30000
RW FVS
Setting of the time within which the
External Fault
alarm must be reset in order to perform automatic restart.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.6
4510 ExtFlt holdoff
ms
UINT16
0
0
10000
RW FVS
Setting of the delay between the signalling of the external fault alarm
ExtFlt
and enabling of the alarm. If an alarm
condition occurs, the drive will wait for the set time before blocking is enabled. If the alarm is removed within the set
time, the drive will not indicate any alarm condition.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.7
4520 MotorOT src
LINK 16
6000
0
16384
RW FVS
Selection of the origin (source) of the signal to be used for the motor overtemperature alarm
MotorOT
. The terminal
that can be used for this function can be selected from among those listed in the “
L_DIGSEL2
” selection list.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.8
4522 MotorOT activity
ENUM
Warning
0
4
RW FVS
Setting of the behaviour of the drive in case of a motor overtemperature alarm
MotorOT
. This alarm indicates that
the motor temperature is too high.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.9
4524 MotorOT restart
ENUM
Disable
0
1
RW FVS
Enabling of automatic restart after the motor overtemperature alarm
MotorOT
.
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.10 4526 TMotorOT restart time
ms
UINT16
1000
120
30000
RW FVS
Setting of the time within which the
Motor Overtemperature
alarm must be reset in order to perform automatic
restart.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.11 4528 MotorOT holdoff
ms
UINT16
1000
0
30000
RW FVS
Setting of the delay between the signalling of the motor overtemperature alarm
MotorOT
and enabling of the alarm.
If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If the alarm is removed
within the set time, the drive will not indicate any alarm condition.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.12 4540 Overspeed threshold
rpm INT32
CALCI
0
CALCI
RW FVS
Setting of the threshold above which the overspeed alarm
Overspeed
is enabled.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.13 4542 Overspeed activity
ENUM
Disable
0
4
RW FVS
Setting of the behaviour of the drive in case of a motor overspeed alarm
Overspeed
. This alarm indicates that the
motor speed has exceeded the threshold set in the
Speed ref top lim
and
Speed ref bottom lim
parameters in the
Содержание SIEIDrive ADV100
Страница 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Страница 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Страница 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Страница 153: ...ADV100 Block Diagrams 153 References ...
Страница 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Страница 155: ...ADV100 Block Diagrams 155 Multireference ...
Страница 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Страница 157: ...ADV100 Block Diagrams 157 Monitor function ...
Страница 158: ...158 ADV100 Block Diagrams ...
Страница 159: ...ADV100 Block Diagrams 159 Commands ...
Страница 160: ...160 ADV100 Block Diagrams ...
Страница 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Страница 162: ...162 ADV100 Block Diagrams Analog inputs ...
Страница 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Страница 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Страница 165: ...ADV100 Block Diagrams 165 Torque config ...
Страница 166: ...166 ADV100 Block Diagrams VF parameters ...
Страница 167: ...ADV100 Block Diagrams 167 Functions ...
Страница 168: ...168 ADV100 Block Diagrams ...
Страница 169: ...ADV100 Block Diagrams 169 ...
Страница 170: ...170 ADV100 Block Diagrams PID application ...
Страница 171: ......