ADV100 • Functions description and parameters list
5 – REFERENCES
ADV drives are provided with a speed regulation circuit, which can be adapted to suit the various applications. In the
standard version, the regulator has PI behaviour and the regulator parameters are the same for the entire field of regu-
lation.
Different sources can be used for the speed and torque references, depending on how the
552 Control mode select
parameter is set.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
5.1
600
Dig ramp ref 1
rpm INT16 16/32
0
CALCI
CALCI
RW FVS
Setting of the digital ramp reference. The speed that the drive must reach after completing the acceleration phase
is set with the ramp reference. Variations in the ramp reference are made with the selected ramp times. The size of
the ramp reference determines the motor speed value. The sign determines the direction of rotation. The
Ramp ref
parameter also refers to a minimum speed, if set. When the “
Motor potentiometer
” or “
Multispeed
” functions are
selected the relative references are used. This reference can only be used in the
Remote
mode.
The overall ramp reference is the result of the sum of the values with the
Ramp ref 1
and
Ramp ref 2
sign.
Example 1:
Ramp ref 1
= + 500 rpm
Ramp ref 2
= + 300 rpm
Ramp ref
= 500 rpm + 300 rpm = 800 rpm
Example 2:
Ramp ref 1
= + 400 rpm
Ramp ref 2
= - 600 rpm
Ramp ref
= 400 rpm – 600 rpm = - 200 rpm
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
5.2
602
Dig ramp ref 2
rpm INT16 16/32
0
CALCI
CALCI
ERW FVS
Setting of the digital ramp reference. The speed that the drive must reach after completing the acceleration phase
is set with the ramp reference. Variations in the ramp reference are made with the selected ramp times. The size of
the ramp reference determines the motor speed value. The sign determines the direction of rotation. The
Ramp ref
parameter also refers to a minimum speed, if set. When the “
Motor potentiometer
” or “
Multispeed
” functions are
selected the relative references are used.
In
Remote
mode the overall ramp reference is the result of the sum of the values with the Ramp ref 1 and Ramp ref
2 sign.
Example 1:
Ramp ref 1
= + 500 rpm
Ramp ref 2
= + 300 rpm
Ramp ref
= 500 rpm + 300 rpm = 800 rpm
Содержание SIEIDrive ADV100
Страница 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Страница 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Страница 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Страница 153: ...ADV100 Block Diagrams 153 References ...
Страница 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Страница 155: ...ADV100 Block Diagrams 155 Multireference ...
Страница 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Страница 157: ...ADV100 Block Diagrams 157 Monitor function ...
Страница 158: ...158 ADV100 Block Diagrams ...
Страница 159: ...ADV100 Block Diagrams 159 Commands ...
Страница 160: ...160 ADV100 Block Diagrams ...
Страница 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Страница 162: ...162 ADV100 Block Diagrams Analog inputs ...
Страница 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Страница 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Страница 165: ...ADV100 Block Diagrams 165 Torque config ...
Страница 166: ...166 ADV100 Block Diagrams VF parameters ...
Страница 167: ...ADV100 Block Diagrams 167 Functions ...
Страница 168: ...168 ADV100 Block Diagrams ...
Страница 169: ...ADV100 Block Diagrams 169 ...
Страница 170: ...170 ADV100 Block Diagrams PID application ...
Страница 171: ......