4. CONFIGURATION
4.13.1. STP.xx - Value of step xx
Acronym
Scrolling message
Submenu
Attributes
STP.xx
CUSTOM LINEARIZATION STEP
LINRZ
R W
The parameter shows and sets the value of the various steps, with xx from 0 to 32.
The low scale value goes in STP.00 and the full-scale value in STP.32.
The value of the nth step corresponds to the input: mV start scale + n*ΔmV con ΔmV = (mV full scale - mV start scale)/32.
Unit of measurement
:
Scale points
Options
:
-1999...9999
4.13.2. MV.STA - Setting mV at start of scale
Acronym
Scrolling message
Submenu
Attributes
MV.STA
MV START SCALE
LINRZ
R W
The parameter shows and sets the value in millivolts at start of scale if the input is a thermocouple.
Unit of measurement
: mV
Options
:
-19.99...99.99
4.13.3. MV.FUL - Setting mV at full scale
Acronym
Scrolling message
Submenu
Attributes
MV.FUL
MV FULL SCALE
LINRZ
R W
The parameter shows and sets the value in millivolts at full scale if the input is a thermocouple.
Unit of measurement
: mV
Options
:
MV.STA + 1...99.99
4.13.4. MV.50C - Setting mV at temperature of 50 °C
Acronym
Scrolling message
Submenu
Attributes
MV.50C
MV AT 50 ‘C
LINRZ
R W
The parameter shows and sets the value in millivolts at 50°C if the input is a thermocouple.
Unit of measurement
: mV
Options
:
-1.999...9.999