80224_MHW_650 L - 1250 L_07-2018_ENG - 49
4.6.11. BLK.AL - Flashing of PV display
Acronym
Scrolling message
Submenu
Attributes
BLK.AL
BLINK DISPLAY PV DEF
ALARM
R W
The parameter shows and sets the flashing of the PV display in case of alarm, for the alarm being configured.
If the parameter is “On,” the value shown on the PV display starts to flash in case of alarm.
The parameter only appears for ALARM=2, ALARM=3 and ALARM=4.
Only On for Alarm 1
Unit of measurement
: -
Options
:
OFF
= PV display does not flash in case of alarm
On
=
The PV display flashes in the event of alarm
4.6.12. BLK.AN - PV display alarm flashing with alarm reset
Acronym
Scrolling message
Submenu
Attributes
BLK.AN
BLINK DISPLAY PV DEF AT ALARM DISACT
ALARM
R W
The parameter controls the optional blinking of the PV value display with regard to latched alarms. The parameter sets PV
display flashing in the case when the alarm is no longer active, but has been latched from prior triggering, but has not yet
been cleared from memory.
If the parameter is “On”, the value displayed on the PV display flashes.
The parameter only appears for ALARM=2, ALARM=3 and ALARM=4.
Only OFF for Alarm 1
The parameter only appears if LATCH=On or OnOF.
Unit of measurement
: -
Options
:
OFF
= The PV display does not flash
On
=
The PV display flashes
4. CONFIGURATION