
80224_MHW_650 L - 1250 L_07-2018_ENG - 60
4. CONFIGURATION
4.11.1. CODE - Identification code
Acronym
Scrolling message
Submenu
Attributes
CODE
INSTRUMENT ID CODE FOR SERIAL COMM
SERIA
R W
The parameter shows and sets the identifying address of the indicator in a Modbus serial network. Generally should not
be set to “1”
Unit of measurement:
Number
Options
:
1...247
4.11.2. KBAUD - Selecting communication speed
Acronym
Scrolling message
Submenu
Attributes
KBAUD
COMMUNICATION SPEED
SERIA
R W
The parameter shows and sets the communication speed for the serial port.
Unit of measurement
: kbaud
Options
:
1.2
= 1200 baud
2.4
= 2400 baud
4.8
= 4800 baud
9.6
= 9600 baud
19.2
= 19200 baud
38.4
= 38400 baud
57.6
= 57600 baud
115.2
= 115200 baud
4.11.3. PAr - Selecting parity
Acronym
Scrolling message
Submenu
Attributes
PAr
PARITY
SERIA
R W
The parameter shows and sets the parity used in serial communication.
Unit of measurement
: -
Options
:
NONE
= No parity
ODD
= Odd parity
EVEN
= Even parity