80224_MHW_650 L - 1250 L_07-2018_ENG - 40
4. CONFIGURATION
4.5.1. tyPE - Selecting sensor type
Acronym
Scrolling message
Submenu
Attributes
tyPE
MAIN INPUT TYPE OF PROBE
I.MAIN
R W
The parameter shows and sets the sensor type of the main input.
The functions for calibrating Custom sensors are on the US.CAL menu.
When a 4...20 mA input is used and the current is less than 2 mA, an Err message is generated and the relay state speci-
fied with the FAUL.T parameters is activated.
The table shows the scale limits for each sensor type or input based on the set number of decimals.
Sensor type
Sensor
Unit of
measurement
Scale limits for
DEC.P = 0
Scale limits for
DEC.P = 1
nominal accuracy limits @ 25°C
DEC.P=0
DEC.P=1
Thermocouple
J
°C
0...1000
0.0...999.9
K
°C
0...1300
0.0...999.9
R
°C
0...1750
0.0...999.9
>100°C
>300°C
S
°C
0...1750
0.0...999.9
T
°C
-200...400
-199.9...400.0
C
°C
0...2300
0.0...999.9
>300°C
D
°C
0...2300
0.0...999.9
>200°C
B
°C
44…1800
n.d.
E
°C
-100…750
-100.0…750.0
L
°C
-200…900
-199.9...900.0
LGOST
°C
0...600
0.0...600.0
U
°C
-200…400
-199.9…400.0
G
°C
0…2300
n.d.
N
°C
0…1300
0.0…999.9
Pt20Rh
Pt40Rh
°C
0...1880
n.d.
Infrared
characteristic
of the
Tc K model
see note
1
°C
10...70
10.0...70.0
2
°C
60...120
60.0...120.0
3
°C
115...165
115.0...165.0
4
°C
140...260
140.0...260.0
Resistance ther-
mometer
PT100
°C
-200...850
-199.9...850.0
PT100
°C
-50...250
-50.0...250.0
JPT100
°C
-200...600
-199.9...600.0
Voltage /Current
0...60 mV
-1999...9999
-199.9...999.9
0...20 mA
4...20 mA
0...10 V
2...10 V
0...5 V
1...5 V
0...1 V
0.2...1 V
Custom
RTD
-1999...9999
-199.9...999.9
0...60 mV
0...20 mA
4...20 mA
0...10 V
2...10 V
0...5 V
1...5 V
0...1 V
0.2...1 V
Note:
the infrared temperature sensor has an output in voltage for direct connection to the input terminals of the indicator. An external ther-
mometer is needed in order to correct the sensor error.
After identifying the work temperature range (for example, 140 – 260°C), bring the process to a temperature near the minimum scale value,
and after reaching it make a note of value A1 indicated by the instrument and of value A2 indicated by the external thermometer. Bring the
process to a temperature near the maximum scale value, and after reaching it make a note of value B1 indicated by the instrument and
of value B2 indicated by the external thermometer. Enable 4-point linearization (see Correcting 4-point input) and enter the four requested
values (A1, B1 and A2, B2).
.