80224_MHW_650 L - 1250 L_07-2018_ENG - 44
4.5.9. HI.SCL - Upper limit of scale
Acronym
Scrolling message
Submenu
Attributes
HI.SCL
INPUT HIGH LIMIT
I.MAIN
R W
The parameter shows and sets the upper limit of the measurement scale used for the main input, based on input (or sen-
sor) type, engineering units, and number of decimals selected.
The lower value of HI.SCL is limited by the value of LO.SCL.
Unit of measurement
:
The one set with the Unit parameter
Options
:
A value in the interval corresponding to the input or sensor type (see tables for LO.SCL parameter).
4.5.10. OF.SCL - Scale offset correction
Acronym
Scrolling message
Submenu
Attributes
OF.SCL
INPUT OFFSET
I.MAIN
R W
The parameter shows and sets the offset applied to the value read in input to make it correspond to the expected value
for a certain temperature. It corrects any constant read error of the sensor.
This offset is applied linearly to all reads; therefore it cannot be used to correct any sensor linearity errors.
Unit of measurement
:
The one set with the Unit parameter
Options
:
-999...999
4.5.11. LO.AL - Lower limit for alarms
Acronym
Scrolling message
Submenu
Attributes
LO.AL
LOW LIMIT FOR ABSOLUTE ALARMS
I.MAIN
R W
The parameter shows and sets, the minimum value for setting an alarm.
Unit of measurement
:
The one used for the alarm limit.
Options
:
-1999...9999
4.5.12. HI.AL - Upper limit for alarms
Acronym
Scrolling message
Submenu
Attributes
HI.AL
HIGH LIMIT FOR ABSOLUTE ALARMS
I.MAIN
R W
The parameter shows and sets the upper limit for defining alarms, i.e., the maximum value for setting an alarm.
Unit of measurement
:
The one used for the alarm limit.
Options
:
-1999...9999
4. CONFIGURATION