80224_MHW_650 L - 1250 L_07-2018_ENG - 54
4.8.5. SWTCH - Output cycle limit alarm
Acronym
Scrolling message
Submenu
Attributes
SWTCH
NUMBER OF SWITCHING CYCLES
OUTPU
R W
The parameter shows and sets the number of cycles (x1000) of the relay, exceeding which the signal is generated OUTX.
SWITCH ALARM where X is the number of output 1 or 2 or 3 or 4 if the output is relay, logic or triac.
The function is disabled if the parameter equals “0”.
Unit of measurement:
Number
Options
:
0...9999
4.8.6. FAULT - State of output with broken input
Acronym
Scrolling message
Submenu
Attributes
FAULT
FAULT OUTPUT STATE
OUTPU
R W
The parameter shows and sets the state (on, off) that the output assumes in case of broken input (Err, Sbr, ...), if the
output is direct or inverse.
Unit of measurement
: -
Options
:
OFF
= Output is off
On
= Output is on
4.8.7. MSG.OU - Selecting the output message
Acronym
Scrolling message
Submenu
Attributes
MSG.OU
NUMBER OF SCROLLING MESSAGE AT OUTPUT ACT
OUTPU
R W
The parameter shows and sets the number of the message assigned to activation of the output, i.e., the scrolling messa-
ge shown on the display.
For more information on scrolling messages, see paragraph “3.1.2.2. Scrolling messages” on page 24.
If the parameter is set to “0” no message will be displayed when the output is activated.
The same message number can be assigned to different outputs.
Unit of measurement
:
Message number
Options
:
0...25
4. CONFIGURATION