80224_MHW_650 L - 1250 L_07-2018_ENG - 25
3.3. First power-on
At first power-on, after the indicator has run the self-diagnostics test, press the
key to access the Fast Configuration
Menu. The parameters shown are a subset of all the indicator parameters and let you rapidly configure the inputs and
outputs.
The number and type of the parameters shown depends on the indicator HW configuration and on the choices made with
the parameters previously shown.
For example, minimum and maximum scale limits are shown only if you have chosen an mA or V type temperature sensor.
Fast Configuration also appears if the HMI menu is set to parameter QuiCk = On
3.3.1. Fast configuration
3. COMMISSIONING
> 2 s
> 2 s
> 2 s
R
R
R
R
R
R
R
R
R
R
R
A
A
Lowers the value
Raises the value
Lowers the value
Raises the value
Minimum scale limit
Only for selected sensors mV or V, the scale limits
LO.SCL, HI.SCL setpoint for TC or RTD sensors
are automatically set according to sensor type and
engineering units.
Maximum scale limit
Only for selected sensors mV or V.
Select engineering unit
The engineering units can be
°C or °F only if a TC or Rtd sensor is selected.
Select sensor type
Home