80224_MHW_650 L - 1250 L_07-2018_ENG - 42
4.5.3. Lin - Linearization type
Acronym
Scrolling message
Submenu
Attributes
Lin
CUSTOM LINEARIZATION
I.MAIN
R W
The parameter sets linearization for the selected sensor type.
The function corrects any linearity and proportionality errors in the correlation between measured value and the actual
value.
T
V
Correlation
of input
Ideal
correlation
This correction can be made with two different algorithms: 32-step linearization and 4-point linearization. Values are set (33 linearization
for 32 steps and 4 for 4-point linearization) with the LINRZ submenu parameters.
For an explanation of 4-point linearization, see paragraph “5.4. 4-point input correction ”5.2. 4-point input correction” on page 73.
Unit of measurement
: -
Options
:
NONE
= No linearization
32.STP
= 32-step linearization
4.POIN
= 4-point linearization
4.5.4. Unit - Displayed engineering units
Acronym
Scrolling message
Submenu
Attributes
Unit
ENGINEERING UNITS
I.MAIN
R W
The parameter shows and sets the engineering units displayed for input 1. The unit appears on the Home page of the
display.
For thermocouple or RTD inputs, the °C / °F selection automatically converts the temperature value; the related scale
limits and setpoint limits must be set.
Unit of measurement
: -
Options
:
NONE
= No unit of measurement
°C
= Degrees Celsius
°F
= Degrees Fahrenheit
CUST
= Custom, settable with GF_eXpress
4.5.5. FILT - Digital filter
Acronym
Scrolling message
Submenu
Attributes
FILT
DIGITAL FILTER
I.MAIN
R W
The parameter shows and sets the value of the digital filter time constant.
With 0.00 no filter is applied.
Unit of measurement
: Seconds
Options
:
0.00...20.00
4. CONFIGURATION