9-6
T35 Transformer Protection System
GE Multilin
9.2 DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES
9 COMMISSIONING
9
d) SLOPE 1 TEST
Inject current in such a manner that the magnitude of
I
r
is larger than the restraint current of 0.67 pu, corresponding to the
intersection of the minimum PKP and Slope 1 and smaller than the Breakpoint 1 setting; that is,
(EQ 9.9)
1.
Change the current magnitudes as follows:
2.
The following differential and restraint current should be read from the T35 actual values menu:
The Percent Differential element will not operate even though
I
d
is larger than the Minimum Pickup, because
I
d
is not large enough to make the
ratio larger than the Slope 1 setting of 15%. The actual ratio is 11.3%.
3.
Adjust the
I
1
current as shown below (thereby increasing
I
d
) and verify that the element operates.
4.
The following differential and restraint current should appear in the T35 actual values menu:
5.
The actual
ratio is now 17%. Verify that the element operates correctly.
WINDING 1
WINDING 2
PHASE SINGLE CURRENT (I
1
)
PHASE SINGLE CURRENT (I
2
)
A
0 A
∠
0°
A
0 A
∠
0°
B
0.48 A
∠
0°
B
1 A
∠
–180°
C
0.48 A
∠
–180°
C
1 A
∠
0°
PHASE DIFFERENTIAL CURRENT (I
d
)
PHASE RESTRAINT CURRENT (I
r
)
A
0
∠
0°
A
0
∠
0°
B
0.113 pu
∠
0°
B
1 pu
∠
–180°
C
0.113 pu
∠
0°
C
1 pu
∠
0°
WINDING 1
WINDING 2
PHASE SINGLE CURRENT (I
1
)
PHASE SINGLE CURRENT (I
2
)
A
0 A
∠
0°
A
0 A
∠
0°
B
0.45 A
∠
0°
B
1 A
∠
–180°
C
0.45 A
∠
–180°
C
1 A
∠
0°
PHASE DIFFERENTIAL CURRENT (I
d
)
PHASE RESTRAINT CURRENT (I
r
)
A
0
∠
0°
A
0
∠
0°
B
0.170 pu
∠
0°
B
1 pu
∠
–180°
C
0.170 pu
∠
0°
C
1 pu
∠
0°
I
r
intersection of Min PKP and Slope 1
(
)
I
r
actual
(
)
I
r
Break 1
(
)
<
<
NOTE
I
d
I
r
⁄
I
d
I
r
⁄
Содержание T35 UR Series
Страница 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Страница 382: ...9 16 T35 Transformer Protection System GE Multilin 9 5 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...