SELECTOR 1 FUNCTION:
“Enabled”
SELECTOR 1 3BIT A0:
“CONT IP 1 ON”
SELECTOR 1 FULL-RANGE:
“4”
SELECTOR 1 3BIT A1:
“CONT IP 2 ON”
SELECTOR 1 STEP-UP MODE:
“Time-out”
SELECTOR 1 3BIT A2:
“CONT IP 3 ON”
SELECTOR 1 TIME-OUT:
“5.0 s”
SELECTOR 1 3BIT MODE:
“Time-out”
SELECTOR 1 STEP-UP:
“PUSHBUTTON 1 ON”
SELECTOR 1 3BIT ACK:
“Off”
SELECTOR 1 ACK:
“Off”
SELECTOR 1 POWER-UP MODE:
“Synchronize”
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the
SETTINGS
INPUTS/OUTPUTS
CONTACT OUTPUTS
menu:
OUTPUT H1 OPERATE:
“SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE:
“SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE:
“SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the
SETTINGS
PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION:
“Self-reset”
PUSHBUTTON 1 DROP-OUT TIME:
“0.10 s”
The logic for the selector switch is shown below:
Figure 5–57: SELECTOR SWITCH LOGIC
842012A2.CDR
step up
acknowledge
3-bit position out
ON
FLEXLOGIC™ OPERANDS
SELECTOR 1 POS 1
SELECTOR 1 POS 2
SELECTOR 1 POS 3
SELECTOR 1 POS 4
SELECTOR 1 POS 5
SELECTOR 1 POS 6
SELECTOR 1 POS 7
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
FLEXLOGIC™ OPERANDS
RUN
SELECTOR 1 POWER-UP MODE:
SETTINGS
SELECTOR 1 TIME-OUT:
SELECTOR 1 STEP-UP MODE:
SELECTOR 1 FULL RANGE:
SELECTOR 1 STEP-UP:
Off = 0
SELECTOR 1 FUNCTION:
SETTINGS
Enabled = 1
SELECTOR 1 ACK:
Off = 0
SELECTOR 1 3BIT A0:
Off = 0
SELECTOR 1 3BIT A1:
Off = 0
SELECTOR 1 3BIT A2:
Off = 0
SELECTOR 1 3BIT ACK:
Off = 0
3-bit acknowledge
SELECTOR 1 POSITION
ACTUAL VALUE
2
1
3
4
5
6
7
SELECTOR 1 3BIT MODE:
SELECTOR 1 PWR ALARM
thr
ee-bit
contr
ol
input
OR
Содержание T35 UR Series
Страница 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Страница 382: ...9 16 T35 Transformer Protection System GE Multilin 9 5 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...