GE Multilin
T35 Transformer Protection System
5-99
5 SETTINGS
5.4 SYSTEM SETUP
5
3.
Configure source
n
(source 2 for this example) as the current from CTY in Winding 1 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(6)
settings menu.
SOURCE 2 NAME:
“WDG 1Y”
SOURCE 2 PHASE CT:
“F5”
SOURCE 2 GROUND CT:
“None”
SOURCE 2 PHASE VT:
“None”
SOURCE 2 AUX VT:
“None”
4.
Configure source
n
(source 3 for this example) to be used as the current in Winding 2 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(6)
settings menu.
SOURCE 3 NAME:
“WDG 2"
SOURCE 3 PHASE CT:
“M1”
SOURCE 3 GROUND CT:
“M1”
SOURCE 3 PHASE VT
: “None”
SOURCE 3 AUX VT:
“None”
5.
Configure the source setting of the transformer windings in the
SYSTEM SETUP
TRANSFORMER
WINDING n
set-
tings menu.
WINDING 1 SOURCE:
“WDG 1X”
WINDING 2 SOURCE:
“WDG 1Y”
WINDING 3 SOURCE:
“WDG 2"
SETUP METHOD B (ALTERNATE)
This approach adds the current from each phase of the CT1 and CT2 together to represent the total winding 1 current. The
procedure is shown below.
1.
Enter the settings for each set of CTs in the
SYSTEM SETUP
AC INPUTS
CURRENT BANK
settings menu, as shown for
Method A above.
2.
Configure Source
n
(Source 1 for this example) to be used as the summed current in Winding 1 in the
SYSTEM SETUP
SIGNAL SOURCES
SOURCE n
settings menu.
SOURCE 1 NAME:
“WDG 1"
SOURCE 1 PHASE CT:
“F1 + F5”
SOURCE 1 GROUND CT:
“None”
SOURCE 1 PHASE VT:
“None”
SOURCE 1 AUX VT:
“None”
3.
Configure Source
n
(Source 2 for this example) to be used as the Winding 2 current in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE n
settings menu.
SOURCE 2 NAME:
“WDG 2"
SOURCE 2 PHASE CT:
“M1”
SOURCE 2 GROUND CT:
“M1”
SOURCE 2 PHASE VT:
“None”
SOURCE 2 AUX VT:
“None”
Содержание T35 UR Series
Страница 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Страница 382: ...9 16 T35 Transformer Protection System GE Multilin 9 5 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...