GE Multilin
T35 Transformer Protection System
5-185
5 SETTINGS
5.9 TRANSDUCER INPUTS AND OUTPUTS
5
5.9.3 DCMA OUTPUTS
PATH: SETTINGS
TRANSDUCER I/O
DCMA OUTPUTS
DCMA OUTPUT F1(W8)
Hardware and software is provided to generate DCmA signals that allow interfacing with external equipment. Specific hard-
ware details are contained in chapter 3. The DCmA output channels are arranged in a manner similar to transducer input or
CT and VT channels. The user configures individual channels with the settings shown below.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an exam-
ple for channel M5 is shown).
The relay checks the driving signal (
x
in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as
MIN VAL
and
MAX VAL
match the output range of the hardware defined as
RANGE
. The follow-
ing equation is applied:
(EQ 5.41)
where:
x
is a driving signal specified by the
SOURCE
setting
I
min
and
I
max
are defined by the
RANGE
setting
k
is a scaling constant calculated as:
(EQ 5.42)
The feature is intentionally inhibited if the
MAX VAL
and
MIN VAL
settings are entered incorrectly, e.g. when
MAX VAL
–
MIN
VAL
< 0.1 pu. The resulting characteristic is illustrated in the following figure.
DCMA OUTPUT F1
DCMA OUTPUT F1
SOURCE: Off
Range: Off, any analog actual value parameter
MESSAGE
DCMA OUTPUT F1
RANGE: –1 to 1 mA
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
MESSAGE
DCMA OUTPUT F1
MIN VAL: 0.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
DCMA OUTPUT F1
MAX VAL: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
I
out
I
min
if
x
MIN VAL
<
I
max
if
x
MAX VAL
>
k x
MIN VAL
–
(
)
I
min
+
otherwise
=
k
I
max
I
min
–
MAX VAL
MIN VAL
–
-------------------------------------------------
=
Содержание T35 UR Series
Страница 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Страница 382: ...9 16 T35 Transformer Protection System GE Multilin 9 5 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...