GEK-113328A
G650 Generator Protection & Control System
3-29
3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
3
Thanks to the use of a double flash memory, one with the Bootcode startup program and the operative system, and a
second one with the application program (firmware), a high reliability is guaranteed when updating the unit firmware, as
even if the case of a communication breakdown during the firmware upgrade process, we can retry the process for an
unlimited number of times.
•
Upgrade 650 web server (Ethernet connection): Go to
“Communications> Upgrade 650 web server”
. The relay web
server application can be updated to further versions (if available) using this menu without modifying the relay
operative system.Upload info files to relay (Ethernet connection): Go to
“Communications>Upload info files to
relay”
. This functionality is used to store setting files (*.650) inside the relay, as well as auxiliary files used by the
programmable logic graphical editor (*.pep, *.aut, *.lib).
•
Download info files from relay (Ethernet connection): Go to
“Communications>Download info files from relay”
.
This functionality is used for retrieving the files (*.650 and *.pep, *.aut, *.lib) that have been previously stored in the
relay flash memory.
Important Note:
*.650 files contain protection, control settings, relay configuration and compiled logic
equations. This file can be retrieved from the relay, using the
“File>Get info from
relay”
option in EnerVista 650 Setup (through serial or Ethernet communication).
“File>Send info to relay”
option stores this *.650 file in the relay.
*.pep, *.aut and *.lib files contain the logic configuration projects necessary to modify the
logic (virtual outputs) in the relay. These files can be stored in the relay, using the
“Communication>Upload info files to relay”
option in EnerVista 650 Setup (through
Ethernet communication). They can be retrieved using
“Communication>Download
info files to relay”
option in EnerVista 650 Setup program (Ethernet communication).
Take into account that the *.pep, *.aut and library files are necessary to modify the PLC
logic (virtual outputs). Without these files setting and configuration can be modified but
not logic equations (virtual outputs). It is advisable to use the
“Communication>Upload info files to relay”
option to store these logic configuration
files into the relay.
It is important to distinguish between “
Send / Get info to relay
” and
“Upload /
Download info files to/from relay”
.
“File>Send/Get info to relay”
sends/gets
settings and configuration and compiled logic equation to/from the relay (*.650 format),
and the relay automatically starts working with the new settings once they are stored.
“
Communications>Upload/Download info files to relay“
,
stores/retrieves
in the
relay hard disk: settings, configuration and compiled logic equations (*.650) besides the
PLC files (*.pep, *.aut, *.lib). This is only a physical storage (file backup).
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...