2-18
G650 Generator Protection & Control System
GEK-113328A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.2.4 PULSE COUNTERS
2.4.2.5 ANALOG COMPARATORS
Level Accuracy
±
0.5% of the reading
±
10 mA from 0.05 to 10 A
±
1.5% of the reading for higher values.
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Number of Pulse counters available
Up to 8
Multiplier factor
0.000 to 65000.000 in steps of 0.001
Overload factor
0 to 1000000 in steps of 1
Board Origin
All available input/outputs boards in the device. See
ordering code [F, G, H, J]
Input origin
up to 32 [depending on the board type selection]
Analog Input
Any analog value available in the device
Analog Maximum Threshold value
-100000.000 to 100000.000 in steps of 0.001
Analog Minimum Threshold value
-100000.000 to 100000.000 in steps of 0.001
Analog Delay
0.00 to 900.00 in steps of 0.01
Analog Hysteresis
0.0 to 50.00 in steps of 0.1
Analog Direction (for activation inside or outside the
deadband)
IN or OUT
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...