GEK-113328A
G650 Generator Protection & Control System
B-17
APPENDIX B
B.1 FACTORY DEFAULT SETTINGS
B
LOSS OF EXCITATION 1 > LOSS OF EXCITATION 2 > LOSS OF EXCITATION 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Center point in Ohms (sec) for Stage 1 Stage 1 Center
10.00
0.01 Ohm
[0.10 : 300.00]
Radius value in Ohms (sec) for Stage
1
Stage 1 Radius
8.00
0.01 Ohm
[0.10 : 300.00]
UV Supervision for stage 1
Stage 1 UV Supv
DISABLED
N/A
[DISABLED – ENABLED]
Trip time for Stage 1
Stage 1 Trip Delay
0.05
0.01 s
[0.00 : 65.54]
Center point in Ohms (sec) for Stage 2 Stage 2 Center
10.00
0.01 Ohm
[0.10 : 300.00]
Radius value in Ohms (sec) for Stage
2
Stage 2 Radius
8.00
0.01 Ohm
[0.10 : 300.00]
UV Supervision for stage 2
Stage 2 UV Supv
DISABLED
N/A
[DISABLED – ENABLED]
Trip time for Stage 2
Stage 2 Trip Delay
0.05
0.01 s
[0.00 : 65.54]
UV Supervision Level for both stages
1 and 2
UV Supv Level
40.0
0.1 V
[0.0 : 500.0]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...