B-10
G650 Generator Protection & Control System
GEK-113328A
B.1 FACTORY DEFAULT SETTINGS
APPENDIX B
B
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND IOC
GROUND IOC 1> GROUND IOC 2 > GROUND IOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A
[PHASOR – RMS]
Pickup level
Pickup Level
30.00
0.01 A
[0.05 : 160.00]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND DIRECTIONAL >
GROUND DIRECTIONAL 1> GROUND DIRECTIONAL 2 > GROUND DIRECTIONAL 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Maximum Torque Angle
MTA
-45
1 Deg
[-90 : +90]
Operation Direction
Direction
FORWARD
N/A
[FORWARD – REVERSE]
Polarization type
Polarization
VO
N/A
[V
0
– I
P
– V
0
+I
P
– V
0
*I
P
]
Block logic type
Block Logic
PERMISSION
N/A
[BLOCK – PERMISSION]
Polarization voltage threshold
Pol V Threshold
10
1 V
[0 : 500]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > RESTRICTED GROUND FAULT (ENHANCED MODELS ONLY) >
RESTRICTED GND FAULT 1> RESTRICTED GND FAULT 2 > RESTRICTED GND FAULT 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Ground Fault Pickup
10.00
0.01 CT
0.02 – 20.00
Function slope
Ground Fault Slope
10.00
0.01%
0.00 – 100.00
Time delay
Ground Fault Delay
0.10
0.01 s
0.00 – 600.00
Snapshot event generation
Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > SENSITIVE GROUND TOC (ENHANCED MODELS
ONLY)
SENSITIVE GROUND TOC 1> SENSITIVE GROUND TOC 2 > SENSITIVE GROUND TOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A
[PHASOR – RMS]
Pickup level
Pickup Level
0.050
0.001 A
[0.005 : 16.000]
Curve shape
Curve
IEEE Ext Inv
N/A
[See list of curves]
Time Dial
TD Multiplier
1.00
0.01 s
[0.00 : 900.00]
Reset type
Reset
INSTANTANEOUS
N/A
[INSTANTANEOUS –
LINEAR]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...